Code of Federal Regulations (alpha)

CFR /  Title 10  /  Part 431  /  Sec. 431.106 Uniform test method for the measurement of energy(other than commercial heat pump water heaters).

* * * * *

(b) * * *

Table 2 to Sec. 431.106--Test Procedures for Commercial Water Heaters and Hot Water Supply Boilers

[Other Than Commercial Heat Pump Water Heaters]----------------------------------------------------------------------------------------------------------------

Test procedure

Energy required for With these

Equipment type efficiency Test procedure compliance on and additional

descriptor after stipulations----------------------------------------------------------------------------------------------------------------Residential-Duty Commercial Uniform Energy 10 CFR Part 430, December 31, 2015***.. None.

Water Heater. Factor. Subpart B,

Appendix E.

Gas-fired Storage and Thermal Use test set-up, May 13, 2013.......... A. For all

Instantaneous Water Heaters Efficiency. equipment, and products, the

and Hot Water Supply Boilers*. procedures in duration of the

subsection standby loss

labeled ``Method test shall be

of Test'' of until whichever

ANSI Z21.10.3- of the following

2011**, Exhibit occurs first

G1. after you begin

to measure the

fuel and/or

electric

consumption: (1)

The first cut-

out after 24

hours or (2) 48

hours, if the

water heater is

not in the

heating mode at

that time.

Standby Loss..... Use test set-up, May 13, 2013.......... B. For oil and

equipment, and gas products,

procedures in the standby loss

subsection in Btu per hour

labeled ``Method must be

of Test'' of calculated as

ANSI Z21.10.3- follows: SL (Btu

2011**, Exhibit per hour) = S (%

G2. per hour) x 8.25

(Btu/gal-F) x

Measured Volume

(gal) x 70

(degrees F).Oil-fired Storage and Thermal ANSI Z21.10.3- May 13, 2013.......... C. For oil-fired

Instantaneous Water Heaters Efficiency. 2011**, Exhibit May 13, 2013.......... products, apply

and Hot Water Supply Boilers*. Standby Loss..... G1. the following in

Use test set-up, conducting the

equipment, and thermal

procedures in efficiency and

subsection standby loss

labeled ``Method tests: (1)

of Test'' of Venting

ANSI Z21.10.3- Requirements--Co

2011**, Exhibit nnect a vertical

G2. length of flue

pipe to the flue

gas outlet of

sufficient

height so as to

meet the minimum

draft specified

by the

manufacturer.

(2) Oil Supply--

Adjust the

burner rate so

that: (a) The

hourly Btu input

rate lies within

2 percent

of the

manufacturer's

specified input

rate, (b) the

CO2 reading

shows the value

specified by the

manufacturer,

(c) smoke in the

flue does not

exceed No. 1

smoke as

measured by the

procedure in

ASTM-D2156-80

(reference for

guidance only,

see Sec.

431.104), and

(d) fuel pump

pressure lies

within 10 percent

of

manufacturer's

specifications.Electric Storage and Standby Loss..... Use test set-up, May 13, 2013.......... D. For electric

Instantaneous Water Heaters. equipment, and products, apply

procedures in the following in

subsection conducting the

labeled ``Method standby loss

of Test'' of test: (1) Assume

ANSI Z21.10.3- that the thermal

2011**, Exhibit efficiency (Et)

G2. of electric

water heaters

with immersed

heating elements

is 98 percent.

(2) Maintain the

electrical

supply voltage

to within

5 percent of the

center of the

voltage range

specified on the

water heater

nameplate. (3)

If the set up

includes

multiple

adjustable

thermostats, set

the highest one

first to yield a

maximum water

temperature in

the specified

range as

measured by the

topmost tank

thermocouple.

Then set the

lower

thermostat(s) to

yield a maximum

mean tank

temperature

within the

specified range.

E. Install water-

tube water

heaters as shown

in Figure 2,

``Arrangement

for Testing

Water-tube Type

Instantaneous

and Circulating

Water Heaters.''----------------------------------------------------------------------------------------------------------------* As to hot water supply boilers with a capacity of less than 10 gallons, these test methods become mandatory on

October 21, 2005. Prior to that time, you may use for these products either (1) these test methods if you rate

the product for thermal efficiency, or (2) the test methods in subpart E if you rate the product for

combustion efficiency as a commercial packaged boiler.

** Incorporated by reference, see Sec. 431.105.*** Because the statute permits use of a conversion factor until the later of December 31, 2015 or one year

after publication of a conversion factor final rule, DOE may amend the mandatory compliance date for use of

this amended test procedure, as necessary.