(a) Except as provided in paragraph (b) of this section, each metal halide lamp fixture manufactured on or after January 1, 2009, and designed to be operated with lamps rated greater than or equal to 150 watts but less than or equal to 500 watts shall contain--
(1) A pulse-start metal halide ballast with a minimum ballast efficiency of 88 percent;
(2) A magnetic probe-start ballast with a minimum ballast efficiency of 94 percent; or
(3) A nonpulse-start electronic ballast with either a minimum ballast efficiency of 92 percent for wattages greater than 250 watts; or a minimum ballast efficiency of 90 percent for wattages less than or equal to 250 watts.
(b) The standards described in paragraph (a) of this section do not apply to--
(1) Metal halide lamp fixtures with regulated lag ballasts;
(2) Metal halide lamp fixtures that use electronic ballasts that operate at 480 volts; or
(3) Metal halide lamp fixtures that;
(i) Are rated only for 150 watt lamps;
(ii) Are rated for use in wet locations; as specified by the National Fire Protection Association in NFPA 70 (incorporated by reference; see Sec. 431.323); and
(iii) Contain a ballast that is rated to operate at ambient air temperatures above 50 [deg]C, as specified in UL 1029, (incorporated by reference; see Sec. 431.323).
(c) Except when the requirements of paragraph (a) of this section are more stringent (i.e., require a larger minimum efficiency value) or as provided by paragraph (e) of this section, each metal halide lamp fixture manufactured on or after February 10, 2017, must contain a metal halide ballast with an efficiency not less than the value determined from the appropriate equation in the following table: ----------------------------------------------------------------------------------------------------------------
Designed to be operated with lamps of Tested input Minimum standard
the following rated lamp wattage voltage[Dagger][Dagger] equation[Dagger][Dagger] %----------------------------------------------------------------------------------------------------------------=50 W and <=100 W........... Tested at 480 V................... (1/(1+1.24xP[supcaret](-0.351))) -
0.020dagger;dagger;=50 W and <=100 W........... All others........................ 1/(1+1.24xP[supcaret](-0.351))100 W and <150dagger; W..... Tested at 480 V................... (1/(1+1.24xP[supcaret](-0.351))) -
0.020100 W and <150dagger; W..... All others........................ 1/(1+1.24xP[supcaret](-0.351))=150 [Dagger] W and <=250 W. Tested at 480 V................... 0.880=150 [Dagger] W and <=250 W. All others........................ For =150 W and <=200 W:
0.880
For 200 W and <=250 W: 1/
(1+0.876xP[supcaret](-0.351))250 W and <=500 W........... Tested at 480 V................... For 250 and <265 W:
0.880
For =265 W and <=500 W:
(1/(1+0.876xP[supcaret](-0.351)) -
0.010250 W and <=500 W........... All others........................ 1/(1+0.876xP[supcaret](-0.351))500 W and <=1000 W.......... Tested at 480 V................... For 500 W and <=750 W:
0.900
For 750 W and <=1000 W:
0.000104xP+0.822
For 500 W and <=1000 W:
may not utilize a probe-start
ballast500 W and <=1000 W.......... All others........................ For 500 W and <=750 W:
0.910
For 750 W and <=1000 W:
0.000104xP+0.832
For 500 W and <=1000 W:
may not utilize a probe-start
ballast----------------------------------------------------------------------------------------------------------------dagger; Includes 150 W fixtures specified in paragraph (b)(3) of this section, that are fixtures rated only for
150 W lamps; rated for use in wet locations, as specified by the NFPA 70 (incorporated by reference, see Sec.
431.323), section 410.4(A); and containing a ballast that is rated to operate at ambient air temperatures
above 50 [deg]C, as specified by UL 1029 (incorporated by reference, see Sec. 431.323).[Dagger] Excludes 150 W fixtures specified in paragraph (b)(3) of this section, that are fixtures rated only for
150 W lamps; rated for use in wet locations, as specified by the NFPA 70, section 410.4(A); and containing a
ballast that is rated to operate at ambient air temperatures above 50 [deg]C, as specified by UL 1029.dagger;dagger; P is defined as the rated wattage of the lamp the fixture is designed to operate.[Dagger][Dagger] Tested input voltage is specified in 10 CFR 431.324.
(d) Except as provided in paragraph (e) of this section, metal halide lamp fixtures manufactured on or after February 10, 2017, that operate lamps with rated wattage 500 W to <=1000 W must not contain a probe-start metal halide ballast.
(e) The standards described in paragraphs (c) and (d) of this section do not apply to--
(1) Metal halide lamp fixtures with regulated-lag ballasts;
(2) Metal halide lamp fixtures that use electronic ballasts that operate at 480 volts; and
(3) Metal halide lamp fixtures that use high-frequency electronic ballasts. [74 FR 12075, Mar. 23, 2009, as amended at 79 FR 7844, Feb. 10, 2014] Subpart T [Reserved]