Code of Federal Regulations (alpha)

CFR /  Title 30  /  Part 57  /  Sec. 57.4660 Work in shafts, raises, or winzes and other activities

During performance of an activity underground described in Table C-2 or when falling sparks or hot metal from work performed in a shaft, raise, or winze could pose a fire hazard--

(a) A multipurpose dry-chemical fire extinguisher shall be at the worksite to supplement the fire extinguishing equipment required by Sec. 57.4600; and

(b) At least one of the following actions shall be taken:

(1) Wet down the area before and after the operation, taking precaution against any hazard of electrical shock.

(2) Isolate any combustible material with noncombustible material.

(3) Shield the activity so that hot metal and sparks cannot cause a fire.

(4) Provide a second person to watch for and extinguish any fire.

Table C-2------------------------------------------------------------------------

Activity Distance Fire hazard------------------------------------------------------------------------Welding or cutting with an More than 1 gallon

electric arc or open flame of combustible

liquid, unless in a

closed, metal

container.Using an open flame to bend or Within 35 feet More than 50 pounds

heat materials of-- of non-fire-

retardant wood.Thawing pipes electrically, except More than 10 pounds

with heat tape of combustible

plastics.---------------------------------------------------Soldering or thawing with an open Within 10 feet Materials in a

flame of-- shaft, raise, or

winze that could be

ignited by hot

metal or sparks.------------------------------------------------------------------------

(5) Cover or bulkhead the opening immediately below and adjacent to the activity with noncombustible material to prevent sparks or hot metal from falling down the shaft, raise, or winze. This alternative applies only to activities involving a shaft, raise, or winze.

(c) The affected area shall be inspected during the first hour after the operation is completed. Additional inspections shall be made or other fire prevention measures shall be taken if a fire hazard continues to exist.

Ventilation Control Measures