Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 141  /  Sec. 141.563 What follow-up action is my system required to take

Follow-up action is required according to the following tables: ------------------------------------------------------------------------

(a) The turbidity of an individual Report to the State by the 10th

filter (or the turbidity of combined of the following month and

filter effluent (CFE) for systems with include the filter number(s),

2 filters that monitor CFE in lieu of corresponding date(s),

individual filters) exceeds 1.0 NTU in turbidity value(s) which

two consecutive recordings 15 minutes exceeded 1.0 NTU, and the

apart. cause (if known) for the

exceedance(s).------------------------------------------------------------------------ ------------------------------------------------------------------------

If a system was required to report to

the State * * * Your system must * * *------------------------------------------------------------------------(b) For three months in a row and Conduct a self-assessment of

turbidity exceeded 1.0 NTU in two the filter(s) within 14 days

consecutive recordings 15 minutes of the day the filter exceeded

apart at the same filter (or CFE for 1.0 NTU in two consecutive

systems with 2 filters that monitor measurements for the third

CFE in lieu of individual filters). straight month unless a CPE as

specified in paragraph (c) of

this section was required.

Systems with 2 filters that

monitor CFE in lieu of

individual filters must

conduct a self assessment on

both filters. The self-

assessment must consist of at

least the following

components: assessment of

filter performance;

development of a filter

profile; identification and

prioritization of factors

limiting filter performance;

assessment of the

applicability of corrections;

and preparation of a filter

self-assessment report.(c) For two months in a row and Arrange to have a comprehensive

turbidity exceeded 2.0 NTU in 2 performance evaluation (CPE)

consecutive recordings 15 minutes conducted by the State or a

apart at the same filter (or CFE for third party approved by the

systems with 2 filters that monitor State not later than 60 days

CFE in lieu of individual filters). following the day the filter

exceeded 2.0 NTU in two

consecutive measurements for

the second straight month. If

a CPE has been completed by

the State or a third party

approved by the State within

the 12 prior months or the

system and State are jointly

participating in an ongoing

Comprehensive Technical

Assistance (CTA) project at

the system, a new CPE is not

required. If conducted, a CPE

must be completed and

submitted to the State no

later than 120 days following

the day the filter exceeded

2.0 NTU in two consecutive

measurements for the second

straight month.------------------------------------------------------------------------ [67 FR 1839, Jan. 14, 2002, as amended at 69 FR 38856, June 29, 2004]