Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 141  /  Sec. 141.570 What does subpart T require that my system report to

This subpart T requires your system to report several items to the State. The following table describes the items which must be reported and the frequency of reporting. Your system is required to report the information described in the following table, if it is subject to the specific requirement shown in the first column. ------------------------------------------------------------------------

Description of

Corresponding requirement information to Frequency

(a) Combined Filter Effluent (1) The total By the 10th of the

Requirements. number of filtered following month.(Sec. Sec. 141.550-141.553). water turbidity

measurements taken

during the month.

(2) The number and By the 10th of the

percentage of following month.

filtered water

turbidity

measurements taken

during the month

which are less

than or equal to

your system's

required 95th

percentile limit.

(3) The date and By the 10th of the

value of any following month.

turbidity

measurements taken

during the month

which exceed the

maximum turbidity

value for your

filtration system.(b) Individual Turbidity (1) That your By the 10th of the

Requirements. system conducted following month.(Sec. Sec. 141.560-141.564). individual filter

turbidity

monitoring during

the month.

(2) The filter By the 10th of the

number(s), following month.

corresponding

date(s), and the

turbidity value(s)

which exceeded 1.0

NTU during the

month, and the

cause (if known)

for the

exceedance(s), but

only if 2

consecutive

measurements

exceeded 1.0 NTU.

(3) If a self- By the 10th of the

assessment is following month

required, the date (or 14 days after

that it was the self-

triggered and the assessment was

date that it was triggered only if

completed. the self-

assessment was

triggered during

the last four

days of the

month)

(4) If a CPE is By the 10th of the

required, that the following month.

CPE is required

and the date that

it was triggered.

(5) Copy of Within 120 days

completed CPE after the CPE was

(1) Results of (i) For systems(Sec. Sec. 141.530-141.536). optional serving 500-9,999

monitoring which by July 1, 2003;

show TTHM levels (ii) For systems

<0.064 mg/l and serving fewer

HAA5 levels <0.048 than 500 by

mg/l (Only if your January 1, 2004.

system wishes to

forgo profiling)

or that your

system has begun

disinfection

(1) A description Anytime your(Sec. Sec. 141.540-141.544). of the proposed system is

change in considering a

disinfection, your significant

system's change to its

disinfection disinfection

profile for practice.

Giardia lamblia

(and, if

necessary,

viruses) and

disinfection

benchmark, and an

analysis of how

the proposed

change will affect

the current levels

of disinfection.------------------------------------------------------------------------ [67 FR 1839, Jan. 14, 2002, as amended at 69 FR 38857, June 29, 2004]