Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 415  /  Sec. 415.364 Pretreatment standards for existing sources (PSES).

(a) Except as provided in 40 CFR 403.7 and 403.13, any existing source subject to this subpart and producing copper sulfate, copper chloride, copper iodide, or copper nitrate which introduces pollutants into a publicly owned treatment works must comply with 40 CFR part 403 and achieve the following pretreatment standards for existing sources (PSES):

Subpart AJ--Copper Sulfate, Copper Chloride, Copper Iodide, Copper

Nitrate------------------------------------------------------------------------

PSES effluent limitations

---------------------------

Average of

Pollutant or pollutant property daily values

Maximum for for 30

any 1 day consecutive

days------------------------------------------------------------------------

Milligrams per liter (mg/

l)

---------------Copper(T)................................... 3.2 1.1Nickel(T)................................... 6.4 2.1Selenium(T)................................. 1.6 0.53------------------------------------------------------------------------ In cases where POTWs find it necessary to impose mass limitations, the following equivalent mass limitations are provided as an alternate: The limitations for copper (T), nickel (T), and selenium (T) are the same as specified in Sec. 415.362(a).

(b) Except as provided in 40 CFR 403.7 and 403.13, any existing source subject to this subpart and producing copper carbonate which introduces pollutants into a publicly owned treatment works must comply with 40 CFR part 403 and achieve the following pretreatment standards for existing sources (PSES):

Subpart AJ--Copper Carbonate------------------------------------------------------------------------

PSES effluent limitations

---------------------------

Average of

Pollutant or pollutant property daily values

Maximum for for 30

any 1 day consecutive

days------------------------------------------------------------------------

Milligrams per liter (mg/

l)

---------------Copper (T).................................. 3.2 1.1Nickel (T).................................. 6.4 2.1Selenium (T)................................ 1.6 0.53------------------------------------------------------------------------ In cases where POTWs find it necessary to impose mass limitations, the following equivalent mass limitations are provided as an alternate: The limitations for copper (T), nickel (T), and selenium (T) are the same as specified in Sec. 415.362(b).