Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this subpart must achieve the following effluent limitations which represent the application of BPT:
Effluent Limitations------------------------------------------------------------------------
Maximum
Regulated parameter Maximum monthly avg.
daily \1\ \1\------------------------------------------------------------------------BOD......................................... 140 37TSS......................................... 88 27Ammonia (as N).............................. 10 4.9[alpha]-Terpineol........................... 0.033 0.016Benzoic acid................................ 0.12 0.071p-Cresol.................................... 0.025 0.014Phenol...................................... 0.026 0.015Zinc........................................ 0.20 0.11
pH.......................................... (\2\) (\2\)------------------------------------------------------------------------\1\ Milligrams per liter (mg/L, ppm)\2\ Within the range 6 to 9. [65 FR 3048, Jan. 19, 2000; 65 FR 14344, Mar. 16, 2000]