Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 63  /  Sec. 63.7143 What definitions apply to this subpart?

Terms used in this subpart are defined in the Clean Air Act, in Sec. 63.2, and in this section as follows:

Bag leak detector system (BLDS) is a type of PM detector used on FF to identify an increase in PM emissions resulting from a broken filter bag or other malfunction and sound an alarm.

Belt conveyor means a conveying device that transports processed stone from one location to another by means of an endless belt that is carried on a series of idlers and routed around a pulley at each end.

Bucket elevator means a processed stone conveying device consisting of a head and foot assembly which supports and drives an endless single or double strand chain or belt to which buckets are attached.

Building means any frame structure with a roof.

Capture system means the equipment (including enclosures, hoods, ducts, fans, dampers, etc.) used to capture and transport PM to a control device.

Control device means the air pollution control equipment used to reduce PM emissions released to the atmosphere from one or more process operations at an LMP.

Conveying system means a device for transporting processed stone from one piece of equipment or location to another location within a plant. Conveying systems include but are not limited to feeders, belt conveyors, bucket elevators and pneumatic systems.

Deviation means any instance in which an affected source, subject to this subpart, or an owner or operator of such a source:

(1) Fails to meet any requirement or obligation established by this subpart, including but not limited to any emission limitation (including any operating limit);

(2) Fails to meet any term or condition that is adopted to implement an applicable requirement in this subpart and that is included in the operating permit for any affected source required to obtain such a permit; or

(3) Fails to meet any emission limitation (including any operating limit) in this subpart during startup, shutdown, or malfunction, regardless of whether or not such failure is allowed by this subpart.

Emission limitation means any emission limit, opacity limit, operating limit, or VE limit.

Emission unit means a lime kiln, lime cooler, storage bin, conveying system transfer point, bulk loading or unloading operation, bucket elevator or belt conveyor at an LMP.

Fugitive emission means PM that is not collected by a capture system.

Hydrator means the device used to produce hydrated lime or calcium hydroxide via the chemical reaction of the lime product with water.

Lime cooler means the device external to the lime kiln (or part of the lime kiln itself) used to reduce the temperature of the lime produced by the kiln.

Lime kiln means the device, including any associated preheater, used to produce a lime product from stone feed by calcination. Kiln types include, but are not limited to, rotary kiln, vertical kiln, rotary hearth kiln, double-shaft vertical kiln, and fluidized bed kiln.

Lime manufacturing plant (LMP) means any plant which uses a lime kiln to produce lime product from limestone or other calcareous material by calcination.

Lime product means the product of the lime kiln calcination process including, calcitic lime, dolomitic lime, and dead-burned dolomite.

Limestone means the material comprised primarily of calcium carbonate (referred to sometimes as calcitic or high calcium limestone), magnesium carbonate, and/or the double carbonate of both calcium and magnesium (referred to sometimes as dolomitic limestone or dolomite).

Monovent means an exhaust configuration of a building or emission control device (e.g., positive pressure FF) that extends the length of the structure and has a width very small in relation to its length (i.e., length-to-width ratio is typically greater than 5:1). The exhaust may be an open vent with or without a roof, louvered vents, or a combination of such features.

Particulate matter (PM) detector means a system that is continuously capable of monitoring PM loading in the exhaust of FF or ESP in order to detect bag leaks, upset conditions, or control device malfunctions and sounds an alarm at a preset level. A PM detector system includes, but is not limited to, an instrument that operates on triboelectric, light scattering, light transmittance, or other effects to continuously monitor relative particulate loadings. A BLDS is a type of PM detector.

Positive pressure FF or ESP means a FF or ESP with the fan(s) on the upstream side of the control device.

Process stone handling operations means the equipment and transfer points between the equipment used to transport processed stone, and includes, storage bins, conveying system transfer points, bulk loading or unloading systems, screening operations, bucket elevators, and belt conveyors.

Processed stone means limestone or other calcareous material that has been processed to a size suitable for feeding into a lime kiln.

Screening operation means a device for separating material according to size by passing undersize material through one or more mesh surfaces (screens) in series and retaining oversize material on the mesh surfaces (screens).

Stack emissions means the PM that is released to the atmosphere from a capture system or control device.

Storage bin means a manmade enclosure for storage (including surge bins) of processed stone prior to the lime kiln.

Transfer point means a point in a conveying operation where the material is transferred to or from a belt conveyor.

Vent means an opening through which there is mechanically induced air flow for the purpose of exhausting from a building air carrying PM emissions from one or more emission units.

Sec. Table 1 to Subpart AAAAA of Part 63--Emission Limits

As required in Sec. 63.7090(a), you must meet each emission limit in the following table that applies to you. ------------------------------------------------------------------------

You must meet the following

For . . . emission limit------------------------------------------------------------------------1. Existing lime kilns and their PM emissions must not exceed

associated lime coolers that did not 0.12 pounds per ton of stone

have a wet scrubber installed and feed (lb/tsf).

operating prior to January 5, 2004.2. Existing lime kilns and their PM emissions must not exceed

associated lime coolers that have a 0.60 lb/tsf. If at any time

wet scrubber, where the scrubber after January 5, 2004 the kiln

itself was installed and operating changes to a dry control

prior to January 5, 2004. system, then the PM emission

limit in item 1 of this Table

1 applies, and the kiln is

hereafter ineligible for the

PM emission limit in item 2 of

this Table 1 regardless of the

method of PM control.3. New lime kilns and their associated PM emissions must not exceed

lime coolers. 0.10 lb/tsf.4. All existing and new lime kilns and Weighted average PM emissions

their associated coolers at your LMP, calculated according to Eq. 2

and you choose to average PM in Sec. 63.7112 must not

emissions, except that any kiln that exceed 0.12 lb/tsf (if you are

is allowed to meet the 0.60 lb/tsf PM averaging only existing kilns)

emission limit is ineligible for or 0.10 lb/tsf (if you are

averaging. averaging only new kilns). If

you are averaging existing and

new kilns, your weighted

average PM emissions must not

exceed the weighted average

emission limit calculated

according to Eq. 3 in Sec.

63.7112, except that no new

kiln and its associated cooler

considered alone may exceed an

average PM emissions limit of

0.10 lb/tsf.5. Stack emissions from all PSH PM emissions must not exceed

operations at a new or existing 0.05 grams per dry standard

affected source. cubic meter (g/dscm).6. Stack emissions from all PSH Emissions must not exceed 7

operations at a new or existing percent opacity.

affected source, unless the stack

emissions are discharged through a wet

scrubber control device.7. Fugitive emissions from all PSH Emissions must not exceed 10

operations at a new or existing percent opacity.

affected source, except as provided by

item 8 of this Table 1.8. All PSH operations at a new or All of the individually

existing affected source enclosed in a affected PSH operations must

building. comply with the applicable PM

and opacity emission

limitations in items 5 through

7 of this Table 1, or the

building must comply with the

following: There must be no VE

from the building, except from

a vent; and vent emissions

must not exceed the stack

emissions limitations in items

5 and 6 of this Table 1.9. Each FF that controls emissions from Emissions must not exceed 7

only an individual, enclosed storage percent opacity.

bin.10. Each set of multiple storage bins You must comply with the

at a new or existing affected source, emission limits in items 5 and

with combined stack emissions. 6 of this Table 1.------------------------------------------------------------------------

Sec. Table 2 to Subpart AAAAA of Part 63--Operating Limits

As required in Sec. 63.7090(b), you must meet each operating limit in the following table that applies to you. ------------------------------------------------------------------------

For . . . You must . . .------------------------------------------------------------------------1. Each lime kiln and each lime cooler Maintain and operate the FF

(if there is a separate exhaust to the such that the BLDS or PM

atmosphere from the associated lime detector alarm condition does

cooler) equipped with an FF. not exist for more than 5

percent of the total operating

time in a 6-month period; and

comply with the requirements

in Sec. 63.7113(d) through

(f) and Table 5 to this

subpart. In lieu of a BLDS or

PM detector maintain the FF

such that the 6-minute average

opacity for any 6-minute block

period does not exceed 15

percent; and comply with the

requirements in Sec.

63.7113(f) and (g) and Table 5

to this subpart.2. Each lime kiln equipped with a wet Maintain the 3-hour block

scrubber. exhaust gas stream pressure

drop across the wet scrubber

greater than or equal to the

pressure drop operating limit

established during the most

recent PM performance test;

and maintain the 3-hour block

scrubbing liquid flow rate

greater than the flow rate

operating limit established

during the most recent

performance test.3. Each lime kiln equipped with an Install a PM detector and

electrostatic precipitator. maintain and operate the ESP

such that the PM detector

alarm is not activated and

alarm condition does not exist

for more than 5 percent of the

total operating time in a 6-

month period, and comply with

Sec. 63.7113(e); or,

maintain the ESP such that the

6-minute average opacity for

any 6-minute block period does

not exceed 15 percent, and

comply with the requirements

in Sec. 63.7113(g); and

comply with the requirements

in Sec. 63.7113(f) and Table

5 to this subpart.4. Each PSH operation subject to a PM Maintain the 3-hour block

limit which uses a wet scrubber. average exhaust gas stream

pressure drop across the wet

scrubber greater than or equal

to the pressure drop operating

limit established during the

PM performance test; and

maintain the 3-hour block

average scrubbing liquid flow

rate greater than or equal to

the flow rate operating limit

established during the

performance test.5. All affected sources................ Prepare a written OM&M; plan;

the plan must include the

items listed in Sec.

63.7100(d) and the corrective

actions to be taken when

required in Table 5 to this

subpart.6. Each emission unit equipped with an a. Vent captured emissions

add-on air pollution control device. through a closed system,

except that dilution air may

be added to emission streams

for the purpose of controlling

temperature at the inlet to an

FF; and

b. Operate each capture/

collection system according to

the procedures and

requirements in the OM&M; plan.------------------------------------------------------------------------

Sec. Table 3 to Subpart AAAAA of Part 63--Initial Compliance With

Emission Limits

As required in Sec. 63.7114, you must demonstrate initial compliance with each emission limitation that applies to you, according to the following table. ------------------------------------------------------------------------

You have

demonstrated

initial

For the following compliance, if

For . . . emission limit . . after following

. the requirements

in Sec. 63.7112

. . .------------------------------------------------------------------------1. All new or existing lime PM emissions must The kiln outlet PM

kilns and their associated lime not exceed 0.12 emissions (and if

coolers (kilns/coolers). lb/tsf for all applicable,

existing kilns/ summed with the

coolers with dry separate cooler

controls, 0.60 lb/ PM emissions),

tsf for existing based on the PM

kilns/coolers emissions

with wet measured using

scrubbers, 0.10 Method 5 in

lb/tsf for all appendix A to

new kilns/ part 60 of this

coolers, or a chapter and the

weighted average stone feed rate

calculated measurement over

according to Eq. the period of

3 in Sec. initial

63.7112. performance test,

do not exceed the

emission limit;

if the lime kiln

is controlled by

an FF or ESP and

you are opting to

monitor PM

emissions with a

BLDS or PM

detector, you

have installed

and are operating

the monitoring

device according

to the

requirements in

Sec. 63.7113(d)

or (e),

respectively; and

if the lime kiln

is controlled by

an FF or ESP and

you are opting to

monitor PM

emissions using a

COMS, you have

installed and are

operating the

COMS according to

the requirements

in Sec.

63.7113(g).2. Stack emissions from all PHS PM emissions must The outlet PM

operations at a new or existing not exceed 0.05 g/ emissions, based

affected source. dscm. on Method 5 or

Method 17 in

appendix A to

part 60 of this

chapter, over the

period of the

initial

performance test

do not exceed

0.05 g/dscm; and

if the emission

unit is

controlled with a

wet scrubber, you

have a record of

the scrubber's

pressure drop and

liquid flow rate

operating

parameters over

the 3-hour

performance test

during which

emissions did not

exceed the

emissions

limitation.3. Stack emissions from all PSH Emissions must not Each of the thirty

operations at a new or existing exceed 7 percent 6-minute opacity

affected source, unless the opacity. averages during

stack emissions are discharged the initial

through a wet scrubber control compliance

device. period, using

Method 9 in

appendix A to

part 60 of this

chapter, does not

exceed the 7

percent opacity

limit. At least

thirty 6-minute

averages must be

obtained.4. Fugitive emissions from all Emissions must not Each of the 6-

PSH operations at a new or exceed 10 percent minute opacity

existing affected source. opacity. averages during

the initial

compliance

period, using

Method 9 in

appendix A to

part 60 of this

chapter, does not

exceed the 10

percent opacity

limit.5. All PSH operations at a new All of the All the PSH

or existing affected source, individually operations

enclosed in building. affected PSH enclosed in the

operations must building have

comply with the demonstrated

applicable PM and initial

opacity emission compliance

limitations for according to the

items 2 through 4 applicable

of this Table 3, requirements for

or the building items 2 through 4

must comply with of this Table 3;

the following: or if you are

There must be no complying with

VE from the the building

building, except emission

from a vent, and limitations,

vent emissions there are no VE

must not exceed from the building

the emission according to item

limitations in 18 of Table 4 to

items 2 and 3 of this subpart and

this Table 3. Sec.

63.7112(k), and

you demonstrate

initial

compliance with

applicable

building vent

emissions

limitations

according to the

requirements in

items 2 and 3 of

this Table 3.6. Each FF that controls Emissions must not Each of the ten 6-

emissions from only an exceed 7 percent minute averages

individual storage bin. opacity. during the 1-hour

initial

compliance

period, using

Method 9 in

appendix A to

part 60 of this

chapter, does not

exceed the 7

percent opacity

limit.

7. Each set of multiple storage You must comply You demonstrate

bins with combined stack with emission initial

emissions. limitations in compliance

items 2 and 3 of according to the

this Table 3. requirements in

items 2 and 3 of

this Table 3.------------------------------------------------------------------------

Sec. Table 4 to Subpart AAAAA of Part 63--Requirements for Performance

Tests

As required in Sec. 63.7112, you must conduct each performance test in the following table that applies to you. ----------------------------------------------------------------------------------------------------------------

According to the

For . . . You must . . . Using . . . following requirements

. . .----------------------------------------------------------------------------------------------------------------1. Each lime kiln and each associated Select the location of Method 1 or 1A of Sampling sites must be

lime cooler, if there is a separate the sampling port and appendix A to part 60 located at the outlet

exhaust to the atmosphere from the the number of traverse of this chapter; and of the control

associated lime cooler. ports. Sec. 63.6(d)(1)(i). device(s) and prior to

any releases to the

atmosphere.2. Each lime kiln and each associated Determine velocity and Method 2, 2A, 2C, 2D, Not applicable.

lime cooler, if there is a separate volumetric flow rate. 2F, or 2G in appendix

exhaust to the atmosphere from the A to part 60 of this

associated lime cooler. chapter.3. Each lime kiln and each associated Conduct gas molecular Method 3, 3A, or 3B in Not applicable.

lime cooler, if there is a separate weight analysis. appendix A to part 60

exhaust to the atmosphere from the of this chapter.

associated lime cooler.4. Each lime kiln and each associated Measure moisture Method 4 in appendix A Not applicable.

lime cooler, if there is a separate content of the stack to part 60 of this

exhaust to the atmosphere from the gas. chapter.

associated lime cooler.5. Each lime kiln and each associated Measure PM emissions... Method 5 in appendix A Conduct the test(s)

lime cooler, if there is a separate to part 60 of this when the source is

exhaust to the atmosphere from the chapter. operating at

associated lime cooler, and which representative

uses a negative pressure PM control operating conditions

device. in accordance with

Sec. 63.7(e); the

minimum sampling

volume must be 0.85

dry standard cubic

meter (dscm) (30 dry

standard cubic foot

(dscf)); if there is a

separate lime cooler

exhaust to the

atmosphere, you must

conduct the Method 5

test of the cooler

exhaust concurrently

with the kiln exhaust

test.6. Each lime kiln and each associated Measure PM emissions... Method 5D in appendix A Conduct the test(s)

lime cooler, if there is a separate to part 60 of this when the source is

exhaust to the atmosphere from the chapter. operating at

associated lime cooler, and which representative

uses a positive pressure FF or ESP. operating conditions

in accordance with

Sec. 63.7(e); if

there is a separate

lime cooler exhaust to

the atmosphere, you

must conduct the

Method 5 test of the

separate cooler

exhaust concurrently

with the kiln exhaust

test.7. Each lime kiln.................... Determine the mass rate Any suitable device.... Calibrate and maintain

of stone feed to the the device according

kiln during the kiln to manufacturer's

PM emissions test. instructions; the

measuring device used

must be accurate to

within 5 percent of

the mass rate of stone

feed over its

operating range.

8. Each lime kiln equipped with a wet Establish the operating Data for the gas stream The continuous pressure

scrubber. limit for the average pressure drop drop measurement

gas stream pressure measurement device device must be

drop across the wet during the kiln PM accurate within plus

scrubber. performance test. or minus 1 percent;

you must collect the

pressure drop data

during the period of

the performance test

and determine the

operating limit

according to Sec.

63.7112(j).9. Each lime kiln equipped with a wet Establish the operating Data from the liquid The continuous

scrubber. limit for the average flow rate measurement scrubbing liquid flow

liquid flow rate to device during the kiln rate measuring device

the scrubber. PM performance test. must be accurate

within plus or minus 1

percent; you must

collect the flow rate

data during the period

of the performance

test and determine the

operating limit

according to Sec.

63.7112(j).10. Each lime kiln equipped with a FF Have installed and have Standard operating According to the

or ESP that is monitored with a PM operating the BLDS or procedures requirements in Sec.

detector. PM detector prior to incorporated into the 63.7113(d) or (e),

the performance test. OM&M; plan. respectively.11. Each lime kiln equipped with a FF Have installed and have Standard operating According to the

or ESP that is monitored with a COMS. operating the COMS procedures requirements in Sec.

prior to the incorporated into the 63.7113(g).

performance test. OM&M; plan and as

required by 40 CFR

part 63, subpart A,

General Provisions and

according to PS-1 of

appendix B to part 60

of this chapter,

except as specified in

Sec. 63.7113(g)(2).12. Each stack emission from a PSH Measure PM emissions... Method 5 or Method 17 The sample volume must

operation, vent from a building in appendix A to part be at least 1.70 dscm

enclosing a PSH operation, or set of 60 of this chapter. (60 dscf); for Method

multiple storage bins with combined 5, if the gas stream

stack emissions, which is subject to being sampled is at

a PM emission limit. ambient temperature,

the sampling probe and

filter may be operated

without heaters; and

if the gas stream is

above ambient

temperature, the

sampling probe and

filter may be operated

at a temperature high

enough, but no higher

than 121 C (250 F), to

prevent water

condensation on the

filter (Method 17 may

be used only with

exhaust gas

temperatures of not

more than 250 F).13. Each stack emission from a PSH Conduct opacity Method 9 in appendix A The test duration must

operation, vent from a building observations. to part 60 of this be for at least 3

enclosing a PSH operation, or set of chapter. hours and you must

multiple storage bins with combined obtain at least

stack emissions, which is subject to thirty, 6-minute

an opacity limit. averages.14. Each stack emissions source from Establish the average Data for the gas stream The pressure drop

a PSH operation subject to a PM or gas stream pressure pressure drop measurement device

opacity limit, which uses a wet drop across the wet measurement device must be accurate

scrubber. scrubber. during the PSH within plus or minus 1

operation stack PM percent; you must

performance test. collect the pressure

drop data during the

period of the

performance test and

determine the

operating limit

according to Sec.

63.7112(j).

15. Each stack emissions source from Establish the operating Data from the liquid The continuous

a PSH operation subject to a PM or limit for the average flow rate measurement scrubbing liquid flow

opacity limit, which uses a wet liquid flow rate to device during the PSH rate measuring device

scrubber. the scrubber. operation stack PM must be accurate

performance test. within plus or minus 1

percent; you must

collect the flow rate

data during the period

of the performance

test and determine the

operating limit

according to Sec.

63.7112(j).16. Each FF that controls emissions Conduct opacity Method 9 in appendix A The test duration must

from only an individual, enclosed, observations. to part 60 of this be for at least 1 hour

new or existing storage bin. chapter. and you must obtain

ten 6-minute averages.17. Fugitive emissions from any PSH Conduct opacity Method 9 in appendix A The test duration must

operation subject to an opacity observations. to part 60 of this be for at least 3

limit. chapter. hours, but the 3-hour

test may be reduced to

1 hour if, during the

first 1-hour period,

there are no

individual readings

greater than 10

percent opacity and

there are no more than

three readings of 10

percent during the

first 1-hour period.18. Each building enclosing any PSH Conduct VE check....... The specifications in The performance test

operation, that is subject to a VE Sec. 63.7112(k). must be conducted

limit. while all affected PSH

operations within the

building are

operating; the

performance test for

each affected building

must be at least 75

minutes, with each

side of the building

and roof being

observed for at least

15 minutes.----------------------------------------------------------------------------------------------------------------

Sec. Table 5 to Subpart AAAAA of Part 63--Continuous Compliance With

Operating Limits

As required in Sec. 63.7121, you must demonstrate continuous compliance with each operating limit that applies to you, according to the following table: ------------------------------------------------------------------------

You must

For the following demonstrate

For . . . operating limit . continuous

. . compliance by . .

.------------------------------------------------------------------------1. Each lime kiln controlled by Maintain the 3- Collecting the wet

a wet scrubber. hour block scrubber

average exhaust operating data

gas stream according to all

pressure drop applicable

across the wet requirements in

scrubber greater Sec. 63.7113

than or equal to and reducing the

the pressure drop data according to

operating limit Sec.

established 63.7113(a);

during the PM maintaining the 3-

performance test; hour block

and maintain the average exhaust

3-hour block gas stream

average scrubbing pressure drop

liquid flow rate across the wet

greater than or scrubber greater

equal to the flow than or equal to

rate operating the pressure drop

limit established operating limit

during the established

performance test. during the PM

performance test;

and maintaining

the 3-hour block

average scrubbing

liquid flow rate

greater than or

equal to the flow

rate operating

limit established

during the

performance test

(the continuous

scrubbing liquid

flow rate

measuring device

must be accurate

within plus or

minus 1% and the

continuous

pressure drop

measurement

device must be

accurate within

plus or minus

1%).

2. Each lime kiln or lime cooler a. Maintain and (i) Operating the

equipped with a FF and using a operate the FF or FF or ESP so that

BLDS, and each lime kiln ESP such that the the alarm on the

equipped with an ESP or FF bag leak or PM bag leak or PM

using a PM detector. detector alarm, detection system

is not activated is not activated

and alarm and an alarm

condition does condition does

not exist for not exist for

more than 5 more than 5

percent of the percent of the

total operating total operating

time in each 6- time in each 6-

month period. month reporting

period; and

continuously

recording the

output from the

BLD or PM

detection system;

and

(ii) Each time the

alarm sounds and

the owner or

operator

initiates

corrective

actions within 1

hour of the

alarm, 1 hour of

alarm time will

be counted (if

the owner or

operator takes

longer than 1

hour to initiate

corrective

actions, alarm

time will be

counted as the

actual amount of

time taken by the

owner or operator

to initiate

corrective

actions); if

inspection of the

FF or ESP system

demonstrates that

no corrective

actions are

necessary, no

alarm time will

be counted.3. Each stack emissions source Maintain the 3- Collecting the wet

from a PSH operation subject to hour block scrubber

an opacity limit, which is average exhaust operating data

controlled by a wet scrubber. gas stream according to all

pressure drop applicable

across the wet requirements in

scrubber greater Sec. 63.7113

than or equal to and reducing the

the pressure drop data according to

operating limit Sec.

established 63.7113(a);

during the PM maintaining the 3-

performance test; hour block

and maintain the average exhaust

3-hour block gas stream

average scrubbing pressure drop

liquid flow rate across the wet

greater than or scrubber greater

equal to the flow than or equal to

rate operating the pressure drop

limit established operating limit

during the established

performance test. during the PM

performance test;

and maintaining

the 3-hour block

average scrubbing

liquid flow rate

greater than or

equal to the flow

rate operating

limit established

during the

performance test

(the continuous

scrubbing liquid

flow rate

measuring device

must be accurate

within 1

% and the

continuous

pressure drop

measurement

device must be

accurate within

1%).4. For each lime kiln or lime a. Maintain and i. Installing,

cooler equipped with a FF or an operate the FF or maintaining,

ESP that uses a COMS as the ESP such that the calibrating and

monitoring device. average opacity operating a COMS

for any 6-minute as required by 40

block period does CFR part 63,

not exceed 15 subpart A,

percent. General

Provisions and

according to PS-1

of appendix B to

part 60 of this

chapter, except

as specified in

Sec.

63.7113(g)(2);

and

ii. Collecting the

COMS data at a

frequency of at

least once every

15 seconds,

determining block

averages for each

6-minute period

and demonstrating

for each 6-minute

block period the

average opacity

does not exceed

15 percent.------------------------------------------------------------------------

Sec. Table 6 to Subpart AAAAA of Part 63--Periodic Monitoring for

Compliance With Opacity and Visible Emissions Limits

As required in Sec. 63.7121 you must periodically demonstrate compliance with each opacity and VE limit that applies to you, according to the following table: ------------------------------------------------------------------------

You must

For the following demonstrate

For . . . emission ongoing compliance

limitation . . . . . .------------------------------------------------------------------------1. Each PSH operation subject to a. 7-10 percent (i) Conducting a

an opacity limitation as opacity, monthly 1-minute

required in Table 1 to this depending on the VE check of each

subpart, or any vents from PSH operation, as emission unit in

buildings subject to an opacity required in Table accordance with

limitation. 1 to this subpart. Sec.

63.7121(e); the

check must be

conducted while

the affected

source is in

operation;

(ii) If no VE are

observed in 6

consecutive

monthly checks

for any emission

unit, you may

decrease the

frequency of VE

checking from

monthly to semi-

annually for that

emission unit; if

VE are observed

during any

semiannual check,

you must resume

VE checking of

that emission

unit on a monthly

basis and

maintain that

schedule until no

VE are observed

in 6 consecutive

monthly checks;

(iii) If no VE are

observed during

the semiannual

check for any

emission unit,

you may decrease

the frequency of

VE checking from

semi-annually to

annually for that

emission unit; if

VE are observed

during any annual

check, you must

resume VE

checking of that

emission unit on

a monthly basis

and maintain that

schedule until no

VE are observed

in 6 consecutive

monthly checks;

and

(iv) If VE are

observed during

any VE check, you

must conduct a 6-

minute test of

opacity in

accordance with

Method 9 of

appendix A to

part 60 of this

chapter; you must

begin the Method

9 test within 1

hour of any

observation of VE

and the 6-minute

opacity reading

must not exceed

the applicable

(i) Conducting a

limit, according to item 8 of monthly VE check

Table 1 to this subpart. of the building,

in accordance

with the

specifications in

Sec.

63.7112(k); the

check must be

conducted while

all the enclosed

PSH operations

are operating;

(ii) The check for

each affected

building must be

at least 5

minutes, with

each side of the

building and roof

being observed

for at least 1

minute;

(iii) If no VE are

observed in 6

consecutive

monthly checks of

the building, you

may decrease the

frequency of

checking from

monthly to semi-

annually for that

affected source;

if VE are

observed during

any semi-annual

check, you must

resume checking

on a monthly

basis and

maintain that

schedule until no

VE are observed

in 6 consecutive

monthly checks;

and

(iv) If no VE are

observed during

the semi-annual

check, you may

decrease the

frequency of

checking from

semi-annually to

annually for that

affected source;

and if VE are

observed during

any annual check,

you must resume

checking of that

emission unit on

a monthly basis

and maintain that

schedule until no

VE are observed

in 6 consecutive

monthly checks

(the source is in

compliance if no

VE are observed

during any of

these checks).------------------------------------------------------------------------

Sec. Table 7 to Subpart AAAAA of Part 63--Requirements for Reports

As required in Sec. 63.7131, you must submit each report in this table that applies to you. ------------------------------------------------------------------------

The report must You must submit

You must submit a . . . contain . . . the report . . .------------------------------------------------------------------------1. Compliance report............ a. If there are no Semiannually

deviations from according to the

any emission requirements in

limitations Sec.

(emission limit, 63.7131(b).

operating limit,

opacity limit,

and VE limit)

that applies to

you, a statement

that there were

no deviations

from the emission

limitations

during the

reporting period;

b. If there were Semiannually

no periods during according to the

which the CMS, requirements in

including any Sec.

operating 63.7131(b).

parameter

monitoring

system, was out-

of-control as

specified in Sec.

63.8(c)(7), a

statement that

there were no

periods during

which the CMS was

out-of-control

during the

reporting period;

c. If you have a Semiannually

deviation from according to the

any emission requirements in

limitation Sec.

(emission limit, 63.7131(b).

operating limit,

opacity limit,

and VE limit)

during the

reporting period,

the report must

contain the

information in

Sec.

63.7131(d);

d. If there were Semiannually

periods during according to the

which the CMS, requirements in

including any Sec.

operating 63.7131(b).

parameter

monitoring

system, was out-

of-control, as

specified in Sec.

63.8(c)(7), the

report must

contain the

information in

Sec.

63.7131(e); and

e. If you had a Semiannually

startup, shutdown according to the

or malfunction requirements in

during the Sec.

reporting period 63.7131(b).

and you took

actions

consistent with

your SSMP, the

compliance report

must include the

information in

Sec.

63.10(d)(5)(i).2. An immediate startup, Actions taken for By fax or

shutdown, and malfunction the event. telephone within

report if you had a startup, 2 working days

shutdown, or malfunction during after starting

the reporting period that is actions

not consistent with your SSMP. inconsistent with

the SSMP.3. An immediate startup, The information in By letter within 7

shutdown, and malfunction Sec. working days

report if you had a startup, 63.10(d)(5)(ii). after the end of

shutdown, or malfunction during the event unless

the reporting period that is you have made

not consistent with your SSMP. alternative

arrangements with

the permitting

authority. See

Sec.

63.10(d)(5)(ii).------------------------------------------------------------------------

Sec. Table 8 to Subpart AAAAA of Part 63--Applicability of General

Provisions to Subpart AAAAA

As required in Sec. 63.7140, you must comply with the applicable General Provisions requirements according to the following table: ----------------------------------------------------------------------------------------------------------------

Summary of Am I subject to this

Citation requirement requirement? Explanations----------------------------------------------------------------------------------------------------------------Sec. 63.1(a)(1)-(4)............. Applicability Yes.............................Sec. 63.1(a)(5)................. .................... No..............................Sec. 63.1(a)(6)................. Applicability Yes.............................Sec. 63.1(a)(7)-(a)(9).......... .................... No..............................Sec. 63.1(a)(10)-(a)(14)........ Applicability....... Yes.............................Sec. 63.1(b)(1)................. Initial Yes............................. Sec. Sec. 63.7081

Applicability and 63.7142 specify

Determination. additional

applicability

determination

requirements.Sec. 63.1(b)(2)................. .................... No..............................Sec. 63.1(b)(3)................. Initial Yes.............................

Applicability

Determination.Sec. 63.1(c)(1)................. Applicability After Yes.............................

Standard

Established.Sec. 63.1(c)(2)................. Permit Requirements. No.............................. Area sources not

subject to subpart

AAAAA, except all

sources must make

initial

applicability

determination.Sec. 63.1(c)(3)................. .................... No..............................Sec. 63.1(c)(4)-(5)............. Extensions, Yes.............................

Notifications.Sec. 63.1(d).................... .................... No..............................Sec. 63.1(e).................... Applicability of Yes.............................

Permit Program.Sec. 63.2....................... Definitions......... ................................ Additional

definitions in Sec.

63.7143.Sec. 63.3(a)-(c)................ Units and Yes.............................

Abbreviations.Sec. 63.4(a)(1)-(a)(2).......... Prohibited Yes.............................

Activities.Sec. 3.4(a)(3)-(a)(5)........... .................... No..............................Sec. 63.4(b)-(c)................ Circumvention, Yes.............................

Severability.Sec. 63.5(a)(1)-(2)............. Construction/ Yes.............................

Reconstruction.Sec. 63.5(b)(1)................. Compliance Dates.... Yes.............................Sec. 63.5(b)(2)................. .................... No..............................Sec. 63.5(b)(3)-(4)............. Construction Yes.............................

Approval,

Applicability.Sec. 63.5(b)(5)................. .................... No..............................Sec. 63.5(b)(6)................. Applicability....... Yes.............................Sec. 63.5(c).................... .................... No..............................Sec. 63.5(d)(1)-(4)............. Approval of Yes.............................

Construction/

Reconstruction.Sec. 63.5(e).................... Approval of Yes.............................

Construction/

Reconstruction.Sec. 63.5(f)(1)-(2)............. Approval of Yes.............................

Construction/

Reconstruction.Sec. 63.6(a).................... Compliance for Yes.............................

Standards and

Maintenance.Sec. 63.6(b)(1)-(5)............. Compliance Dates.... Yes.............................Sec. 63.6(b)(6)................. .................... No..............................Sec. 63.6(b)(7)................. Compliance Dates.... Yes.............................Sec. 63.6(c)(1)-(2)............. Compliance Dates.... Yes.............................Sec. 63.6(c)(3)-(c)(4).......... .................... No..............................Sec. 63.6(c)(5)................. Compliance Dates.... Yes.............................Sec. 63.6(d).................... .................... No..............................Sec. 63.6(e)(1)................. Operation & Yes............................. See Sec. 63.7100

Maintenance. for OM&M;

requirements.Sec. 63.6(e)(2)................. .................... No..............................Sec. 63.6(e)(3)................. Startup, Shutdown Yes.............................

Malfunction Plan.Sec. 63.6(f)(1)-(3)............. Compliance with Yes.............................

Emission Standards.Sec. 63.6(g)(1)-(g)(3).......... Alternative Standard Yes.............................

Sec. 63.6(h)(1)-(2)............. Opacity/VE Standards Yes.............................

Sec. 63.6(h)(3)................. .................... No..............................

Sec. 63.6(h)(4)-(h)(5)(i)....... Opacity/VE Standards Yes............................. This requirement

only applies to

opacity and VE

performance checks

required in Table 4

to subpart AAAAA.

Sec. 63.6(h)(5) (ii)-(iii)...... Opacity/VE Standards No.............................. Test durations are

specified in

subpart AAAAA;

subpart AAAAA takes

precedence.Sec. 63.6(h)(5)(iv)............. Opacity/VE Standards No..............................Sec. 63.6(h)(5)(v).............. Opacity/VE Standards Yes.............................Sec. 63.6(h)(6)................. Opacity/VE Standards Yes.............................Sec. 63.6(h)(7)................. COM Use............. Yes.............................Sec. 63.6(h)(8)................. Compliance with Yes.............................

Opacity and VE.Sec. 63.6(h)(9)................. Adjustment of Yes.............................

Opacity Limit.Sec. 63.6(i)(1)-(i)(14)......... Extension of Yes.............................

Compliance.Sec. 63.6(i)(15)................ .................... No..............................Sec. 63.6(i)(16)................ Extension of Yes.............................

Compliance.Sec. 63.6(j).................... Exemption from Yes.............................

Compliance.Sec. 63.7(a)(1)-(a)(3).......... Performance Testing Yes............................. Sec. 63.7110

Requirements. specifies

deadlines; Sec.

63.7112 has

additional specific

requirements.Sec. 63.7(b).................... Notification........ Yes.............................Sec. 63.7(c).................... Quality Assurance/ Yes.............................

Test Plan.Sec. 63.7(d).................... Testing Facilities.. Yes.............................Sec. 63.7(e)(1)-(4)............. Conduct of Tests.... Yes.............................Sec. 63.7(f).................... Alternative Test Yes.............................

Method.Sec. 63.7(g).................... Data Analysis....... Yes.............................Sec. 63.7(h).................... Waiver of Tests..... Yes.............................Sec. 63.8(a)(1)................. Monitoring Yes............................. See Sec. 63.7113.

Requirements.Sec. 63.8(a)(2)................. Monitoring.......... Yes.............................Sec. 63.8(a)(3)................. .................... No..............................Sec. 63.8(a)(4)................. Monitoring.......... No.............................. Flares not

applicable.Sec. 63.8(b)(1)-(3)............. Conduct of Yes.............................

Monitoring.Sec. 63.8(c)(1)-(3)............. CMS Operation/ Yes.............................

Maintenance.Sec. 63.8(c)(4)................. CMS Requirements.... No.............................. See Sec. 63.7121.Sec. 63.8(c)(4)(i)-(ii)......... Cycle Time for COM Yes............................. No CEMS are required

and CEMS. under subpart

AAAAA; see Sec.

63.7113 for CPMS

requirements.Sec. 63.8(c)(5)................. Minimum COM Yes............................. COM not required.

procedures.Sec. 63.8(c)(6)................. CMS Requirements.... No.............................. See Sec. 63.7113.Sec. 63.8(c)(7)-(8)............. CMS Requirements.... Yes.............................Sec. 63.8(d).................... Quality Control..... No.............................. See Sec. 63.7113.Sec. 63.8(e).................... Performance No..............................

Evaluation for CMS.Sec. 63.8(f)(1)-(f)(5).......... Alternative Yes.............................

Monitoring Method.Sec. 63.8(f)(6)................. Alternative to No..............................

Relative Accuracy

test.Sec. 63.8(g)(1)-(g)(5).......... Data Reduction; Data No.............................. See data reduction

That Cannot Be Used. requirements in

Sec. Sec.

63.7120 and

63.7121.Sec. 63.9(a).................... Notification Yes............................. See Sec. 63.7130.

Requirements.Sec. 63.9(b).................... Initial Yes.............................

Notifications.Sec. 63.9(c).................... Request for Yes.............................

Compliance

Extension.Sec. 63.9(d).................... New Source Yes.............................

Notification for

Special Compliance

Requirements.Sec. 63.9(e).................... Notification of Yes.............................

Performance Test.Sec. 63.9(f).................... Notification of VE/ Yes............................. This requirement

Opacity Test. only applies to

opacity and VE

performance tests

required in Table 4

to subpart AAAAA.

Notification not

required for VE/

opacity test under

Table 6 to subpart

AAAAA.Sec. 63.9(g).................... Additional CMS No.............................. Not required for

Notifications. operating parameter

monitoring.Sec. 63.9(h)(1)-(h)(3).......... Notification of Yes.............................

Compliance Status.Sec. 63.9(h)(4)................. .................... No..............................Sec. 63.9(h)(5)-(h)(6).......... Notification of Yes.............................

Compliance Status.Sec. 63.9(i).................... Adjustment of Yes.............................

Deadlines.Sec. 63.9(j).................... Change in Previous Yes.............................

Information.

Sec. 63.10(a)................... Recordkeeping/ Yes............................. See Sec. Sec.

Reporting General 63.7131 through

Requirements. 63.7133.Sec. 63.10(b)(1)-(b)(2)(xii).... Records............. Yes.............................Sec. 63.10(b)(2)(xiii).......... Records for Relative No..............................

Accuracy Test.Sec. 63.10(b)(2)(xiv)........... Records for Yes.............................

Notification.Sec. 63.10(b)(3)................ Applicability Yes.............................

Determinations.Sec. 63.10(c)................... Additional CMS No.............................. See Sec. 63.7132.

Recordkeeping.Sec. 63.10(d)(1)................ General Reporting Yes.............................

Requirements.Sec. 63.10(d)(2)................ Performance Test Yes.............................

Results.Sec. 63.10(d)(3)................ Opacity or VE Yes............................. For the periodic

Observations. monitoring

requirements in

Table 6 to subpart

AAAAA, report

according to Sec.

63.10(d)(3) only if

VE observed and

subsequent visual

opacity test is

required.Sec. 63.10(d)(4)................ Progress Reports.... Yes.............................Sec. 63.10(d)(5)................ Startup, Shutdown, Yes.............................

Malfunction Reports.Sec. 63.10(e)................... Additional CMS No.............................. See specific

Reports. requirements in

subpart AAAAA, see

Sec. 63.7131.Sec. 63.10(f)................... Waiver for Yes.............................

Recordkeeping/

Reporting.Sec. 63.11(a)-(b)............... Control Device No.............................. Flares not

Requirements. applicable.Sec. 63.12(a)-(c)............... State Authority and Yes.............................

Delegations.Sec. 63.13(a)-(c)............... State/Regional Yes.............................

Addresses.Sec. 63.14(a)-(b)............... Incorporation by No..............................

Reference.Sec. 63.15(a)-(b)............... Availability of Yes.............................

Information.----------------------------------------------------------------------------------------------------------------

Subpart BBBBB_National Emission Standards for Hazardous Air Pollutants

for Semiconductor Manufacturing

Source: 68 FR 27925, May 22, 2003, unless otherwise noted.

What This Subpart Covers