Code of Federal Regulations (alpha)

CFR /  Title 46  /  Part 111  /  Sec. 111.60-7 Demand loads.

Generator, feeder, and bus-tie cables must be selected on the basis of a computed load of not less than the demand load given in Table 111.60-7.

Table 111.60-7--Demand Loads------------------------------------------------------------------------

Type of circuit Demand load------------------------------------------------------------------------Generator cables...................... 115 percent of continuous

generator rating.Switchboard bus-tie, except ship's 75 percent of generating

service to emergency switchboard bus- capacity of the larger

tie. switchboard.Emergency switchboard bus-tie......... 115 percent of continuous rating

of emergency generator.Motor feeders......................... Article 430, NFPA NEC 2002

(incorporated by reference; see

46 CFR 110.10-1).Galley equipment feeder............... 100 percent of either the first

50 KW or one-half the connected

load, whichever is the larger,

plus 65 percent of the

remaining connected load, plus

50 percent of the rating of the

spare switches or circuit

breakers on the distribution

panel.Lighting feeder....................... 100 percent of the connected

load plus the average active

circuit load for the spare

switches or circuit breakers on

the distribution panels.Grounded neutral of a dual voltage 100 percent of the capacity of

feeder. the ungrounded conductors when

grounded neutral is not

protected by a circuit breaker

overcurrent trip, or not less

than 50 percent of the capacity

of the ungrounded conductors

when the grounded neutral is

protected by a circuit breaker

overcurrent trip or overcurrent

alarm.------------------------------------------------------------------------ [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2004-18884, 69 FR 58348, Sept. 30, 2004; USCG-2003-16630, 73 FR 65198, Oct. 31, 2008]