CFR /  Title 46  /  Part 112  /  Sec. 112.20-15 Transfer of emergency loads.

(a) When the potential of the final emergency power source reaches 85 to 95 percent of normal value, the emergency loads under Sec. 112.15-5 must transfer automatically to the final emergency power source and, on a passenger vessel, this transfer must be accomplished in no more than 45 seconds after failure of the normal source of power.

(b) When the potential from the normal source has been restored, the emergency loads must be manually or automatically transferred to the normal source, and the final emergency power source must be manually or automatically stopped.

(c) If the potential of the final emergency power source is less than 75 to 85 percent of normal value while supplying the emergency loads, the temporary emergency loads under Sec. 112.15-1 must transfer automatically to the temporary emergency power source.

Subpart 112.25_Emergency Systems Having an Automatic Starting Diesel

Engine or Gas Turbine Driven Emergency Power Source as the Sole

Emergency Power Source