Code of Federal Regulations (alpha)

CFR /  Title 46  /  Part 115  /  Sec. 115.810 Fire protection.

(a) At each initial and subsequent inspection for certification, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment, including the following:

(1) Inspection of each hand portable fire extinguisher, semiportable fire extinguisher, and fixed gas fire extinguishing system to check for excessive corrosion and general condition;

(2) Inspection of piping, controls, and valves, and the inspection and testing of alarms and ventilation shutdowns, for each fixed gas fire extinguishing system and detecting system to determine that the system is in operating condition;

(3) Operation of the fire main system and checking of the pressure at the most remote and highest outlets;

(4) Testing of each firehose to a test pressure equivalent to its maximum service pressure;

(5) Checking of each cylinder containing compressed gas to ensure it has been tested and marked in accordance with Sec. 147.60 in subchapter N of this chapter;

(6) Testing or renewal of flexible connections and discharge hoses on semiportable extinguishers and fixed gas extinguishing systems in accordance with Sec. 147.65 in subchapter N of this chapter; and

(7) Inspection and testing of smoke and fire detecting systems (including sensors and alarms) and fire confining appliances (such as fire screen doors and fire dampers).

(b) The owner, managing operator, or a qualified servicing facility as applicable shall conduct the following inspections and tests:

(1) For portable fire extinguishers, the inspections, maintenance procedures and hydrostatic pressure tests required by Chapter 4 of NFPA 10, ``Portable Fire Extinguishers,'' with the frequency specified by NFPA 10. In addition, carbon dioxide and halon portable fire extinguishers must be refilled when the net content weight loss exceeds that specified for fixed systems by Table 115.810(b). The owner or managing operator shall provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records have not been properly maintained, a qualified servicing facility may be required to perform the required inspections, maintenance procedures, and hydrostatic pressure tests. A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted.

(2) For semiportable and fixed gas fire extinguishing systems, the inspections and tests required by Table 115.810(b), in addition to the tests required by Sec. Sec. 147.60 and 147.65 in subchapter N of this chapter. The owner or managing operator shall provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records have not been properly maintained, a qualified servicing facility may be required to perform the required inspections, maintenance procedures, and hydrostatic pressure tests.

Table 115.810(b)--Semiportable and Fixed Fire Extinguishing Systems------------------------------------------------------------------------

Type system Test------------------------------------------------------------------------Carbon dioxide................ Weigh cylinders. Recharge cylinder if

weight loss exceeds 10 percent of the

weight of the charge. Test time delays,

alarms, and ventilation shutdowns with

carbon dioxide, nitrogen, or other

nonflammable gas as stated in the

system manufacturer's instruction

manual. Inspect hoses for damage or

decay. Ensure that nozzles are

unobstructed. Cylinders must be tested

and marked, and all flexible

connections on fixed carbon dioxide

systems must be tested or renewed, as

required by 46 CFR 147.60 and 147.65.Halon 1301 and halocarbon..... Recharge or replace if weight loss

exceeds 5 percent of the weight of the

charge or if cylinder has a pressure

gauge, recharge cylinder if pressure

loss exceeds 10 percent, adjusted for

temperature. Test time delays, alarms,

and ventilation shutdowns with carbon

dioxide, nitrogen, or other

nonflammable gas as stated in the

system manufacturer's instruction

manual. Inspect hoses for damage or

decay. Ensure that nozzles are

unobstructed. Cylinders must be tested

and marked, and all flexible

connections to Halon 1301 and

halocarbon cylinders must be tested or

renewed, as required by 46 CFR 147.60

and 147.65 or 147.67. Note that Halon

1301 system approvals have expired, but

that existing systems may be retained

if they are in good and serviceable

condition to the satisfaction of the

Coast Guard inspector.Dry chemical (cartridge Examine pressure cartridge and replace

operated). if end is punctured, has leaked, or is

otherwise unsuitable. Inspect hose and

nozzle to see if they are clear. Insert

charged cartridge. Ensure dry chemical

is free flowing, not caked, and

extinguisher contains full charge.Dry chemical (stored pressure) See that pressure gauge is in the

operating range. If not, or if the seal

is broken, weigh or otherwise determine

that extinguisher is fully charged with

dry chemical. Recharge cylinder if

pressure is low or if dry chemical is

needed.Foam (stored pressure)........ See that the pressure gauge is in the

operating range. If not, or if the seal

is broken, weigh or otherwise determine

that extinguisher is fully charged with

foam. Recharge cylinder if pressure is

low or if foam is needed. Replace

premixed agent every 3 years.

Inert gas..................... Recharge or replace cylinder if cylinder

pressure loss exceeds 5 percent of the

specified gauge pressure, adjusted for

temperature. Test time delays, alarms,

and ventilation shutdowns with carbon

dioxide, nitrogen, or other

nonflammable gas as stated in the

system manufacturer's instruction

manual. Inspect hoses for damage or

decay. Ensure that nozzles are

unobstructed. Cylinders must be tested

and marked, and all flexible

connections on fixed inert

extinguishers must be tested or renewed

as required by 46 CFR 147.60 and

147.66.Water mist.................... Maintain system in accordance with

maintenance instructions in system

manufacturer's design, installation,

operation, and maintenance manual.------------------------------------------------------------------------

(c) The owner, managing operator, or master shall destroy, in the presence of the marine inspector, each fire hose found to be defective and incapable of repair.

(d) At each initial and subsequent inspection for certification, the marine inspector may require that a fire drill be held under simulated emergency conditions to be specified by the inspector. [CGD 85-080, 61 FR 892, Jan. 10, 1996, as amended at 62 FR 51348, Sept. 30, 1997; USCG-2006-24797, 77 FR 33882, June 7, 2012]