Code of Federal Regulations (alpha)

CFR /  Title 46  /  Part 91  /  Sec. 91.25-20 Fire extinguishing equipment.

(a) At each inspection for certification, periodic inspection and at other times necessary, the inspector will determine that all fire-extinguishing equipment is in suitable condition and may require any tests necessary to determine the condition of the equipment. The inspector will determine if the tests and inspections required by Sec. 97.15-60 of this subchapter have been conducted. At each inspection for certification and periodic inspection, the inspector will check fire-extinguishing equipment with the following tests and inspections:

(1) All hand portable fire extinguishers and semi-portable fire extinguishing systems shall be checked as noted in Table 91.25-20(a)(1). In addition, the hand portable fire extinguishers and semi-portable fire extinguishing systems shall be examined for excessive corrosion and general condition.

Table 91.25-20(a)(1)------------------------------------------------------------------------

Type unit Test------------------------------------------------------------------------Soda acid................................ Discharge. Clean hose and

inside of extinguisher

thoroughly. Recharge.Foam..................................... Discharge. Clean hose and

inside of extinguisher

thoroughly. Recharge.Pump tank (water or antifreeze).......... Discharge. Clean hose and

inside of extinguisher

thoroughly. Recharge with

clean water or antifreeze.Cartridge operated (water, antifreeze or Examine pressure cartridge

loaded stream). and replace if end is

punctured or if cartridge is

otherwise determined to have

leaked or to be in

unsuitable condition. Remove

liquid. Clean hose and

inside of extinguisher

thoroughly. Recharge with

clean water, solution, or

antifreeze. Insert charged

cartridge.Carbon Dioxide........................... Weigh cylinders. Recharge if

weight loss exceeds 10

percent of weight of charge.

Inspect hose and nozzle to

be sure they are clear. \1\Dry chemical (cartridge-operated type)... Examine pressure cartridge

and replace if end is

punctured or if cartridge is

otherwise determined to have

leaked or to be in

unsuitable condition.

Inspect hose and nozzle to

see they are clear. Insert

charged cartridge. Be sure

dry chemical is free-flowing

(not caked) and chamber

contains full charge.Dry chemical (stored pressure type)...... See that pressure gage is in

operating range. If not, or

if seal is broken, weigh or

otherwise determine that

full charge of dry chemical

is in extinguisher. Recharge

if pressure is low or if dry

chemical is needed.Vaporizing liquid \2\ (pump type)........ Pump a few strokes into clean

pail and replace liquid.

Keep water out of

extinguisher or liquid. Keep

extinguisher completely full

of liquid.Vaporizing liquid \2\ (stored pressure See that pressure gage is in

type). operating range. Weigh or

check liquid level to

determine that full charge

of liquid is in

extinguisher. Recharge if

pressure is low or if liquid

is needed.------------------------------------------------------------------------\1\ Cylinders must be tested and marked, and all flexible connections

and discharge hoses of semi-portable carbon dioxide and halon

extinguishers must be tested or renewed, as required by Sec. Sec.

147.60 and 147.65 of this chapter.\2\ Vaporizing-liquid type fire extinguishers containing carbon

tetrachloride or chlorobromomethane or other toxic vaporizing liquids

shall be removed from all vessels. (See Sec. 95.50-5(e) of this

subchapter.)

(2) Fixed fire-extinguishing systems shall be checked as noted in Table 91.25-20(a)(2). In addition, all parts of the fixed fire-extinguishing systems, shall be examined for excessive corrosion and general conditions.

Table 91.25-20(a)(2)------------------------------------------------------------------------

Type system Test------------------------------------------------------------------------Foam.................................. Systems utilizing a soda

solution must have that

solution replaced. In all

cases, ascertain that powder is

not caked

Carbon dioxide........................ Weigh cylinders. Recharge

cylinder if weight loss exceeds

10 percent of the weight of the

charge. Test time delays,

alarms, and ventilation

shutdowns with carbon dioxide,

nitrogen, or other nonflammable

gas as stated in the system

manufacturer's instruction

manual. Inspect hoses for

damage or decay. Ensure that

nozzles are unobstructed.

Cylinders must be tested and

marked, and all flexible

connections on fixed carbon

dioxide systems must be tested

or renewed, as required by 46

CFR 147.60 and 147.65Halon 1301 and halocarbon............. Recharge or replace if weight

loss exceeds 5 percent of the

weight of the charge or if

cylinder has a pressure gauge,

recharge cylinder if pressure

loss exceeds 10 percent,

adjusted for temperature. Test

time delays, alarms, and

ventilation shutdowns with

carbon dioxide, nitrogen, or

other nonflammable gas as

stated in the system

manufacturer's instruction

manual. Inspect hoses for

damage or decay. Ensure that

nozzles are unobstructed.

Cylinders must be tested and

marked, and all flexible

connections to Halon 1301 and

halocarbon cylinders must be

tested or renewed, as required

by 46 CFR 147.60 and 147.65 or

147.67.

NOTE: Halon 1301 system

approvals have expired, but

existing systems may be

retained if they are in good

and serviceable condition to

the satisfaction of the Coast

Guard inspector.Inert gas............................. Recharge or replace cylinder if

cylinder pressure loss exceeds

5 percent of the specified

gauge pressure, adjusted for

temperature. Test time delays,

alarms, and ventilation

shutdowns with carbon dioxide,

nitrogen, or other nonflammable

gas as stated in the system

manufacturer's instruction

manual. Ensure that nozzles are

unobstructed. Cylinders must be

tested and marked, and all

flexible connections on fixed

inert extinguishers must be

tested or renewed, as required

by 46 CFR 147.60 and 147.66.Water mist............................ Maintain system in accordance

with the maintenance

instructions in the system

manufacturer's design,

installation, operation, and

maintenance manual.------------------------------------------------------------------------

(3) On all fire-extinguishing systems, all piping controls, valves, and alarms shall be checked to ascertain that the system is in operating condition. In this respect steam smothering lines shall be checked with at least a 50 p.s.i. air pressure with the ends capped or by blowing steam through the lines at the designed pressure.

(4) The fire main system shall be operated and the pressure checked at the most remote and highest outlets. All firehose shall be subjected to a test pressure equivalent to the maximum pressure to which they may be subjected in service, but not less than 100 p.s.i. [CGFR 65-50, 30 FR 16974, Dec. 30, 1965, as amended by CGFR 68-32, 33 FR 5718, Apr. 18, 1968; CGD 78-154, 44 FR 13491, Mar. 12, 1979; CGD 84-044, 53 FR 7748, Mar. 10, 1988; USCG-1999-4976, 65 FR 6501, Feb. 9, 2000; 65 FR 11904, Mar. 7, 2000; USCG-2006-24797, 77 FR 33877, June 7, 2012]