CFR /  Title 30  /  Part 18  /  Sec. 18.24 Electrical clearances.

Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:

Minimum Clearances Between Uninsulated Surfaces------------------------------------------------------------------------

Clearances (inches)

-----------------------

Phase-to-

Phase-to-Phase Voltage (rms) Phase-to- Ground or

Phase Control

Circuit------------------------------------------------------------------------0 to 250........................................ 0.25 0.25251 to 600...................................... 0.28 0.25601 to 1000..................................... 0.61 0.251001 to 2400.................................... 1.4 0.62401 to 4160.................................... 3.0 1.4------------------------------------------------------------------------ [57 FR 61209, Dec. 23, 1992]