CFR /  Title 40  /  Part 141  /  Sec. 141.623 Reduced monitoring.

(a) You may reduce monitoring to the level specified in the table in this paragraph (a) any time the LRAA is <=0.040 mg/L for TTHM and <=0.030 mg/L for HAA5 at all monitoring locations. You may only use data collected under the provisions of this subpart or subpart L of this part to qualify for reduced monitoring. In addition, the source water annual average TOC level, before any treatment, must be <=4.0 mg/L at each treatment plant treating surface water or ground water under the direct influence of surface water, based on monitoring conducted under either Sec. 141.132(b)(1)(iii) or Sec. 141.132(d). ----------------------------------------------------------------------------------------------------------------

Distribution system

Source water type Population Monitoring frequency \1\ monitoring location per

size category monitoring period----------------------------------------------------------------------------------------------------------------Subpart H:

<500 .......................... monitoring may not be

reduced.

500-3,300 per year.................. 1 TTHM and 1 HAA5 sample:

one at the location and

during the quarter with

the highest TTHM single

measurement, one at the

location and during the

quarter with the highest

HAA5 single measurement;

1 dual sample set per

year if the highest TTHM

and HAA5 measurements

occurred at the same

location and quarter.

3,301-9,999 per year.................. 2 dual sample sets: one at

the location and during

the quarter with the

highest TTHM single

measurement, one at the

location and during the

quarter with the highest

HAA5 single measurement.

10,000-49,999 per quarter............... 2 dual sample sets at the

locations with the

highest TTHM and highest

HAA5 LRAAs.

50,000-249,999 per quarter............... 4 dual sample sets--at the

locations with the two

highest TTHM and two

highest HAA5 LRAAs.

250,000-999,99 per quarter............... 6 dual sample sets--at the

9 locations with the three

highest TTHM and three

highest HAA5 LRAAs.

1,000,000-4,99 per quarter............... 8 dual sample sets--at the

9,999 locations with the four

highest TTHM and four

highest HAA5 LRAAs.

=5, per quarter............... 10 dual sample sets--at

000,000 the locations with the

five highest TTHM and

five highest HAA5 LRAAs.Ground Water:

<500 every third year.......... 1 TTHM and 1 HAA5 sample:

one at the location and

during the quarter with

the highest TTHM single

measurement, one at the

location and during the

quarter with the highest

HAA5 single measurement;

1 dual sample set per

year if the highest TTHM

and HAA5 measurements

occurred at the same

location and quarter.

500-9,999 per year.................. 1 TTHM and 1 HAA5 sample:

one at the location and

during the quarter with

the highest TTHM single

measurement, one at the

location and during the

quarter with the highest

HAA5 single measurement;

1 dual sample set per

year if the highest TTHM

and HAA5 measurements

occurred at the same

location and quarter.

10,000-99,999 per year.................. 2 dual sample sets: one at

the location and during

the quarter with the

highest TTHM single

measurement, one at the

location and during the

quarter with the highest

HAA5 single measurement.

100,000-499,99 per quarter............... 2 dual sample sets; at the

9 locations with the

highest TTHM and highest

HAA5 LRAAs.

=50 per quarter............... 4 dual sample sets at the

0,000 locations with the two

highest TTHM and two

highest HAA5 LRAAs.----------------------------------------------------------------------------------------------------------------\1\ Systems on quarterly monitoring must take dual sample sets every 90 days.

(b) You may remain on reduced monitoring as long as the TTHM LRAA <=0.040 mg/L and the HAA5 LRAA <=0.030 mg/L at each monitoring location (for systems with quarterly reduced monitoring) or each TTHM sample <=0.060 mg/L and each HAA5 sample <=0.045 mg/L (for systems with annual or less frequent monitoring). In addition, the source water annual average TOC level, before any treatment, must be <=4.0 mg/L at each treatment plant treating surface water or ground water under the direct influence of surface water, based on monitoring conducted under either Sec. 141.132(b)(1)(iii) or Sec. 141.132(d).

(c) If the LRAA based on quarterly monitoring at any monitoring location exceeds either 0.040 mg/L for TTHM or 0.030 mg/L for HAA5 or if the annual (or less frequent) sample at any location exceeds either 0.060 mg/L for TTHM or 0.045 mg/L for HAA5, or if the source water annual average TOC level, before any treatment, 4.0 mg/L at any treatment plant treating surface water or ground water under the direct influence of surface water, you must resume routine monitoring under Sec. 141.621 or begin increased monitoring if Sec. 141.625 applies.

(d) The State may return your system to routine monitoring at the State's discretion.