Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this subpart must achieve the following effluent limitations which represent the application of BPT:
Effluent Limitations------------------------------------------------------------------------
Maximum
Regulated parameter Maximum monthly avg.
daily \1\ \1\------------------------------------------------------------------------BOD5........................................ 220 56TSS......................................... 88 27Ammonia (as N).............................. 10 4.9[alpha]-Terpineol........................... 0.042 0.019Aniline..................................... 0.024 0.015Benzoic acid................................ 0.119 0.073Naphthalene................................. 0.059 0.022p-Cresol.................................... 0.024 0.015Phenol...................................... 0.048 0.029Pyridine.................................... 0.072 0.025Arsenic..................................... 1.1 0.54Chromium.................................... 1.1 0.46Zinc........................................ 0.535 0.296pH.......................................... (\2\) (\2\)------------------------------------------------------------------------\1\ Milligrams per liter (mg/L, ppm).\2\ Within the range 6 to 9. [65 FR 3048, Jan. 19, 2000; 65 FR 14344, Mar. 16, 2000]