Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 63  /  Sec. 63.2406 What definitions apply to this subpart?

Terms used in this subpart are defined in the CAA, in Sec. 63.2, 40 CFR part 63, subparts H, PP, SS, TT, UU, and WW, and in this section. If the same term is defined in another subpart and in this section, it will have the meaning given in this section for purposes of this subpart. Notwithstanding the introductory language in Sec. 63.921, the terms ``container'' and ``safety device'' shall have the meaning found in this subpart and not in Sec. 63.921.

Actual annual average temperature, for organic liquids, means the temperature determined using the following methods:

(1) For heated or cooled storage tanks, use the calculated annual average temperature of the stored organic liquid as determined from a design analysis of the storage tank.

(2) For ambient temperature storage tanks:

(i) Use the annual average of the local (nearest) normal daily mean temperatures reported by the National Climatic Data Center; or

(ii) Use any other method that the EPA approves.

Annual average true vapor pressure means the equilibrium partial pressure exerted by the total table 1 organic HAP in the stored or transferred organic liquid. For the purpose of determining if a liquid meets the definition of an organic liquid, the vapor pressure is determined using standard conditions of 77 degrees F and 29.92 inches of mercury. For the purpose of determining whether an organic liquid meets the applicability criteria in table 2, items 1 through 6, to this subpart, use the actual annual average temperature as defined in this subpart. The vapor pressure value in either of these cases is determined:

(1) In accordance with methods described in American Petroleum Institute Publication 2517, Evaporative Loss from External Floating-Roof Tanks (incorporated by reference, see Sec. 63.14);

(2) Using standard reference texts;

(3) By the American Society for Testing and Materials Method D2879-83, 96 (incorporated by reference, see Sec. 63.14); or

(4) Using any other method that the EPA approves.

Bottoms receiver means a tank that collects distillation bottoms before the stream is sent for storage or for further processing downstream.

Cargo tank means a liquid-carrying tank permanently attached and forming an integral part of a motor vehicle or truck trailer. This term also refers to the entire cargo tank motor vehicle or trailer. For the purpose of this subpart, vacuum trucks used exclusively for maintenance or spill response are not considered cargo tanks.

Closed vent system means a system that is not open to the atmosphere and is composed of piping, ductwork, connections, and, if necessary, flow-inducing devices that transport gas or vapors from an emission point to a control device. This system does not include the vapor collection system that is part of some transport vehicles or the loading arm or hose that is used for vapor return. For transfer racks, the closed vent system begins at, and includes, the first block valve on the downstream side of the loading arm or hose used to convey displaced vapors.

Combustion device means an individual unit of equipment, such as a flare, oxidizer, catalytic oxidizer, process heater, or boiler, used for the combustion of organic emissions.

Container means a portable unit in which a material can be stored, transported, treated, disposed of, or otherwise handled. Examples of containers include, but are not limited to, drums and portable cargo containers known as ``portable tanks'' or ``totes.''

Control device means any combustion device, recovery device, recapture device, or any combination of these devices used to comply with this subpart. Such equipment or devices include, but are not limited to, absorbers, adsorbers, condensers, and combustion devices. Primary condensers, steam strippers, and fuel gas systems are not considered control devices.

Crude oil means any of the naturally occurring liquids commonly referred to as crude oil, regardless of specific physical properties. Only those crude oils downstream of the first point of custody transfer after the production field are considered crude oils in this subpart.

Custody transfer means the transfer of hydrocarbon liquids after processing and/or treatment in the producing operations, or from storage tanks or automatic transfer facilities to pipelines or any other forms of transportation.

Design evaluation means a procedure for evaluating control devices that complies with the requirements in Sec. 63.985(b)(1)(i).

Deviation means any instance in which an affected source subject to this subpart, or portion thereof, or an owner or operator of such a source:

(1) Fails to meet any requirement or obligation established by this subpart including, but not limited to, any emission limitation (including any operating limit) or work practice standard;

(2) Fails to meet any term or condition that is adopted to implement an applicable requirement in this subpart, and that is included in the operating permit for any affected source required to obtain such a permit; or

(3) Fails to meet any emission limitation (including any operating limit) or work practice standard in this subpart during SSM.

Emission limitation means an emission limit, opacity limit, operating limit, or visible emission limit.

Equipment leak component means each pump, valve, and sampling connection system used in organic liquids service at an OLD operation. Valve types include control, globe, gate, plug, and ball. Relief and check valves are excluded.

Gasoline means any petroleum distillate or petroleum distillate/alcohol blend having a Reid vapor pressure of 27.6 kilopascals (4.0 pounds per square inch absolute (psia)) or greater which is used as a fuel for internal combustion engines. Aviation gasoline is included in this definition.

High throughput transfer rack means those transfer racks that transfer into transport vehicles (for existing affected sources) or into transport vehicles and containers (for new affected sources) a total of 11.8 million liters per year or greater of organic liquids.

In organic liquids service means that an equipment leak component contains or contacts organic liquids having 5 percent by weight or greater of the organic HAP listed in Table 1 to this subpart.

Low throughput transfer rack means those transfer racks that transfer into transport vehicles (for existing affected sources) or into transport vehicles and containers (for new affected sources) less than 11.8 million liters per year of organic liquids.

On-site or on site means, with respect to records required to be maintained by this subpart or required by another subpart referenced by this subpart, that records are stored at a location within a major source which encompasses the affected source. On-site includes, but is not limited to, storage at the affected source to which the records pertain, storage in central files elsewhere at the major source, or electronically available at the site.

Organic liquid means:

(1) Any non-crude oil liquid or liquid mixture that contains 5 percent by weight or greater of the organic HAP listed in Table 1 to this subpart, as determined using the procedures specified in Sec. 63.2354(c).

(2) Any crude oils downstream of the first point of custody transfer.

(3) Organic liquids for purposes of this subpart do not include the following liquids:

(i) Gasoline (including aviation gasoline), kerosene (No. 1 distillate oil), diesel (No. 2 distillate oil), asphalt, and heavier distillate oils and fuel oils;

(ii) Any fuel consumed or dispensed on the plant site directly to users (such as fuels for fleet refueling or for refueling marine vessels that support the operation of the plant);

(iii) Hazardous waste;

(iv) Wastewater;

(v) Ballast water: or

(vi) Any non-crude oil liquid with an annual average true vapor pressure less than 0.7 kilopascals (0.1 psia).

Organic liquids distribution (OLD) operation means the combination of activities and equipment used to store or transfer organic liquids into, out of, or within a plant site regardless of the specific activity being performed. Activities include, but are not limited to, storage, transfer, blending, compounding, and packaging.

Permitting authority means one of the following:

(1) The State Air Pollution Control Agency, local agency, or other agency authorized by the EPA Administrator to carry out a permit program under 40 CFR part 70; or

(2) The EPA Administrator, in the case of EPA-implemented permit programs under title V of the CAA (42 U.S.C. 7661) and 40 CFR part 71.

Plant site means all contiguous or adjoining surface property that is under common control, including surface properties that are separated only by a road or other public right-of-way. Common control includes surface properties that are owned, leased, or operated by the same entity, parent entity, subsidiary, or any combination.

Research and development facility means laboratory and pilot plant operations whose primary purpose is to conduct research and development into new processes and products, where the operations are under the close supervision of technically trained personnel, and which are not engaged in the manufacture of products for commercial sale, except in a de minimis manner.

Responsible official means responsible official as defined in 40 CFR 70.2 and 40 CFR 71.2, as applicable.

Safety device means a closure device such as a pressure relief valve, frangible disc, fusible plug, or any other type of device that functions exclusively to prevent physical damage or permanent deformation to a unit or its air emission control equipment by venting gases or vapors directly to the atmosphere during unsafe conditions resulting from an unplanned, accidental, or emergency event.

Shutdown means the cessation of operation of an OLD affected source, or portion thereof (other than as part of normal operation of a batch-type operation), including equipment required or used to comply with this subpart, or the emptying and degassing of a storage tank. Shutdown as defined here includes, but is not limited to, events that result from periodic maintenance, replacement of equipment, or repair.

Startup means the setting in operation of an OLD affected source, or portion thereof (other than as part of normal operation of a batch-type operation), for any purpose. Startup also includes the placing in operation of any individual piece of equipment required or used to comply with this subpart including, but not limited to, control devices and monitors.

Storage tank means a stationary unit that is constructed primarily of nonearthen materials (such as wood, concrete, steel, or reinforced plastic) that provide structural support and is designed to hold a bulk quantity of liquid. Storage tanks do not include:

(1) Units permanently attached to conveyances such as trucks, trailers, rail cars, barges, or ships;

(2) Pressure vessels designed to operate in excess of 204.9 kilopascals and without emissions to the atmosphere;

(3) Bottoms receivers;

(4) Surge control vessels;

(5) Vessels storing wastewater; or

(6) Reactor vessels associated with a manufacturing process unit.

Surge control vessel means feed drums, recycle drums, and intermediate vessels. Surge control vessels are used within chemical manufacturing processes when in-process storage, mixing, or management of flow rates or volumes is needed to assist in production of a product.

Tank car means a car designed to carry liquid freight by rail, and including a permanently attached tank.

Total actual annual facility-level organic liquid loading volume means the total facility-level actual volume of organic liquid loaded for transport within or out of the facility through transfer racks that are part of the affected source into transport vehicles (for existing affected sources) or into transport vehicles and containers (for new affected sources) based on a 3-year rolling average, calculated annually.

(1) For existing affected sources, each 3-year rolling average is based on actual facility-level loading volume during each calendar year (January 1 through December 31) in the 3-year period. For calendar year 2004 only (the first year of the initial 3-year rolling average), if an owner or operator of an affected source does not have actual loading volume data for the time period from January 1, 2004, through February 2, 2004 (the time period prior to the effective date of the OLD NESHAP), the owner or operator shall compute a facility-level loading volume for this time period as follows: At the end of the 2004 calendar year, the owner or operator shall calculate a daily average facility-level loading volume (based on the actual loading volume for February 3, 2004, through December 31, 2004) and use that daily average to estimate the facility-level loading volume for the period of time from January 1, 2004, through February 2, 2004. The owner or operator shall then sum the estimated facility-level loading volume from January 1, 2004, through February 2, 2004, and the actual facility-level loading volume from February 3, 2004, through December 31, 2004, to calculate the annual facility-level loading volume for calendar year 2004.

(2)(i) For new affected sources, the 3-year rolling average is calculated as an average of three 12-month periods. An owner or operator must select as the beginning calculation date with which to start the calculations as either the initial startup date of the new affected source or the first day of the calendar month following the month in which startup occurs. Once selected, the date with which the calculations begin cannot be changed.

(i) For new affected sources, the 3-year rolling average is calculated as an average of three 12-month periods. An owner or operator must select as the beginning calculation date with which to start the calculations as either the initial startup date of the new affected source or the first day of the calendar month following the month in which startup occurs. Once selected, the date with which the calculations begin cannot be changed.

(ii) The initial 3-year rolling average is based on the projected maximum facility-level annual loading volume for each of the 3 years following the selected beginning calculation date. The second 3-year rolling average is based on actual facility-level loading volume for the first year of operation plus a new projected maximum facility-level annual loading volume for second and third years following the selected beginning calculation date. The third 3-year rolling average is based on actual facility-level loading volume for the first 2 years of operation plus a new projected maximum annual facility-level loading volume for the third year following the beginning calculation date. Subsequent 3-year rolling averages are based on actual facility-level loading volume for each year in the 3-year rolling average.

Transfer rack means a single system used to load organic liquids into, or unload organic liquids out of, transport vehicles or containers. It includes all loading and unloading arms, pumps, meters, shutoff valves, relief valves, and other piping and equipment necessary for the transfer operation. Transfer equipment and operations that are physically separate (i.e., do not share common piping, valves, and other equipment) are considered to be separate transfer racks.

Transport vehicle means a cargo tank or tank car.

Vapor balancing system means:

(1) A piping system that collects organic HAP vapors displaced from transport vehicles or containers during loading and routes the collected vapors to the storage tank from which the liquid being loaded originated or to another storage tank connected to a common header. For containers, the piping system must route the displaced vapors directly to the appropriate storage tank or to another storage tank connected to a common header in order to qualify as a vapor balancing system; or

(2) A piping system that collects organic HAP vapors displaced from the loading of a storage tank and routes the collected vapors to the transport vehicle from which the storage tank is filled.

Vapor collection system means any equipment located at the source (i.e., at the OLD operation) that is not open to the atmosphere; that is composed of piping, connections, and, if necessary, flow-inducing devices; and that is used for:

(1) Containing and conveying vapors displaced during the loading of transport vehicles to a control device;

(2) Containing and directly conveying vapors displaced during the loading of containers; or

(3) Vapor balancing. This does not include any of the vapor collection equipment that is installed on the transport vehicle.

Vapor-tight transport vehicle means a transport vehicle that has been demonstrated to be vapor-tight. To be considered vapor-tight, a transport vehicle equipped with vapor collection equipment must undergo a pressure change of no more than 250 pascals (1 inch of water) within 5 minutes after it is pressurized to 4,500 pascals (18 inches of water). This capability must be demonstrated annually using the procedures specified in EPA Method 27 of 40 CFR part 60, appendix A. For all other transport vehicles, vapor tightness is demonstrated by performing the U.S. DOT pressure test procedures for tank cars and cargo tanks.

Work practice standard means any design, equipment, work practice, or operational standard, or combination thereof, that is promulgated pursuant to section 112(h) of the CAA. [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42911, July 28, 2006]

Sec. Table 1 to Subpart EEEE of Part 63--Organic Hazardous Air

Pollutants

You must use the organic HAP information listed in the following table to determine which of the liquids handled at your facility meet the HAP content criteria in the definition of Organic Liquid in Sec. 63.2406. ------------------------------------------------------------------------

Compound name CAS No.\1\------------------------------------------------------------------------2,4-D salts and esters..................................... 94-75-7Acetaldehyde............................................... 75-07-0Acetonitrile............................................... 75-05-8Acetophenone............................................... 98-86-2Acrolein................................................... 107-02-8Acrylamide................................................. 79-06-1Acrylic acid............................................... 79-10-7Acrylonitrile.............................................. 107-13-1Allyl chloride............................................. 107-05-1Aniline.................................................... 62-53-3Benzene.................................................... 71-43-2Biphenyl................................................... 92-52-4Butadiene (1,3-)........................................... 106-99-0Carbon tetrachloride....................................... 56-23-5Chloroacetic acid.......................................... 79-11-8Chlorobenzene.............................................. 108-90-7

2-Chloro-1,3-butadiene (Chloroprene)....................... 126-99-8Chloroform................................................. 67-66-3m-Cresol................................................... 108-39-4o-Cresol................................................... 95-48-7p-Cresol................................................... 106-44-5Cresols/cresylic acid...................................... 1319-77-3Cumene..................................................... 98-82-8Dibenzofurans.............................................. 132-64-9Dibutylphthalate........................................... 84-74-2Dichloroethane (1,2-) (Ethylene dichloride) (EDC).......... 107-06-2Dichloropropene (1,3-)..................................... 542-75-6Diethanolamine............................................. 111-42-2Diethyl aniline (N,N-)..................................... 121-69-7Diethylene glycol monobutyl ether.......................... 112-34-5Diethylene glycol monomethyl ether......................... 111-77-3Diethyl sulfate............................................ 64-67-5Dimethyl formamide......................................... 68-12-2Dimethylhydrazine (1,1-)................................... 57-14-7Dioxane (1,4-) (1,4-Diethyleneoxide)....................... 123-91-1Epichlorohydrin (1-Chloro-2,3-epoxypropane)................ 106-89-8Epoxybutane (1,2-)......................................... 106-88-7Ethyl acrylate............................................. 140-88-5Ethylbenzene............................................... 100-41-4Ethyl chloride (Chloroethane).............................. 75-00-3Ethylene dibromide (Dibromomethane)........................ 106-93-4Ethylene glycol............................................ 107-21-1Ethylene glycol dimethyl ether............................. 110-71-4Ethylene glycol monomethyl ether........................... 109-86-4Ethylene glycol monomethyl ether acetate................... 110-49-6Ethylene glycol monophenyl ether........................... 122-99-6Ethylene oxide............................................. 75-21-8Ethylidene dichloride (1,1-Dichloroethane)................. 75-34-3Formaldehyde............................................... 50-00-0Hexachloroethane........................................... 67-72-1Hexane..................................................... 110-54-3Hydroquinone............................................... 123-31-9Isophorone................................................. 78-59-1Maleic anhydride........................................... 108-31-6Methanol................................................... 67-56-1Methyl chloride (Chloromethane)............................ 74-87-3Methylene chloride (Dichloromethane)....................... 75-09-2Methylenedianiline (4,4'-)................................. 101-77-9Methylene diphenyl diisocyanate............................ 101-68-8Methyl hydrazine........................................... 60-34-4Methyl isobutyl ketone (Hexone) (MIBK)..................... 108-10-1Methyl methacrylate........................................ 80-62-6Methyl tert-butyl ether (MTBE)............................. 1634-04-4Naphthalene................................................ 91-20-3Nitrobenzene............................................... 98-95-3Phenol..................................................... 108-9-52Phthalic anhydride......................................... 85-44-9Polycyclic organic matter.................................. 50-32-8Propionaldehyde............................................ 123-38-6Propylene dichloride (1,2-Dichloropropane)................. 78-87-5Propylene oxide............................................ 75-56-9Quinoline.................................................. 91-22-5Styrene.................................................... 100-42-5Styrene oxide.............................................. 96-09-3Tetrachloroethane (1,1,2,2-)............................... 79-34-5Tetrachloroethylene (Perchloroethylene).................... 127-18-4Toluene.................................................... 108-88-3Toluene diisocyanate (2,4-)................................ 584-84-9o-Toluidine................................................ 95-53-4Trichlorobenzene (1,2,4-).................................. 120-82-1Trichloroethane (1,1,1-) (Methyl chloroform)............... 71-55-6Trichloroethane (1,1,2-) (Vinyl trichloride)............... 79-00-5Trichloroethylene.......................................... 79-01-6Triethylamine.............................................. 121-44-8Trimethylpentane (2,2,4-).................................. 540-84-1Vinyl acetate.............................................. 108-05-4Vinyl chloride (Chloroethylene)............................ 75-01-4Vinylidene chloride (1,1-Dichloroethylene)................. 75-35-4Xylene (m-)................................................ 108-38-3Xylene (o-)................................................ 95-47-6

Xylene (p-)................................................ 106-42-3Xylenes (isomers and mixtures)............................. 1330-20-7------------------------------------------------------------------------\1\ CAS numbers refer to the Chemical Abstracts Services registry number

assigned to specific compounds, isomers, or mixtures of compounds. [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42913, July 28, 2006]

Sec. Table 2 to Subpart EEEE of Part 63--Emission Limits

As stated in Sec. 63.2346, you must comply with the emission limits for the organic liquids distribution emission sources as follows: ----------------------------------------------------------------------------------------------------------------

If you own or operate . . . And if . . . Then you must . . .----------------------------------------------------------------------------------------------------------------1. A storage tank at an existing affected a. The stored organic liquid is not i. Reduce emissions of

source with a capacity =18.9 crude oil and if the annual average total organic HAP (or,

cubic meters (5,000 gallons) and <189.3 true vapor pressure of the total Table upon approval, TOC) by at

cubic meters (50,000 gallons). 1 organic HAP in the stored organic least 95 weight-percent

liquid is =27.6 kilopascals or, as an option, to an

(4.0 psia) and <76.6 kilopascals (11.1 exhaust concentration less

psia). than or equal to 20 ppmv,

on a dry basis corrected

to 3 percent oxygen for

combustion devices using

supplemental combustion

air, by venting emissions

through a closed vent

system to any combination

of control devices meeting

the applicable

requirements of 40 CFR

part 63, subpart SS; OR

ii. Comply with the work

practice standards

specified in table 4 to

this subpart, items 1.a,

1.b, or 1.c for tanks

storing liquids described

in that table.

b. The stored organic liquid is crude i. See the requirement in

oil. item 1.a.i or 1.a.ii of

this table.2. A storage tank at an existing affected a. The stored organic liquid is not i. See the requirement in

source with a capacity =189.3 crude oil and if the annual average item 1.a.i or 1.a.ii of

cubic meters (50,000 gallons). true vapor pressure of the total Table this table.

1 organic HAP in the stored organic

liquid is <76.6 kilopascals (11.1

psia).

b. The stored organic liquid is crude i. See the requirement in

oil. item 1.a.i or 1.a.ii of

this table.3. A storage tank at a reconstructed or a. The stored organic liquid is not i. See the requirement in

new affected source with a capacity =18.9 cubic meters (5,000 true vapor pressure of the total Table this table.

gallons) and <37.9 cubic meters (10,000 1 organic HAP in the stored organic

gallons). liquid is =27.6 kilopascals

(4.0 psia) and <76.6 kilopascals (11.1

psia).

b. The stored organic liquid is crude i. See the requirement in

oil. item 1.a.i or 1.a.ii of

this table.4. A storage tank at a reconstructed or a. The stored organic liquid is not i. See the requirement in

new affected source with a capacity =37.9 cubic meters (10,000 true vapor pressure of the total Table this table.

gallons) and <189.3 cubic meters (50,000 1 organic HAP in the stored organic

gallons). liquid is =0.7 kilopascals

(0.1 psia) and <76.6 kilopascals (11.1

psia).

b. The stored organic liquid is crude i. See the requirement in

oil. item 1.a.i or 1.a.ii of

this table.5. A storage tank at a reconstructed or a. The stored organic liquid is not i. See the requirement in

new affected source with a capacity =189.3 cubic meters (50,000 true vapor pressure of the total Table this table.

gallons). 1 organic HAP in the stored organic

liquid is <76.6 kilopascals (11.1

psia).

b. The stored organic liquid is crude i. See the requirement in

oil. item 1.a.i or 1.a.ii of

this table.

6. A storage tank at an existing, a. The stored organic liquid is not i. Reduce emissions of

reconstructed, or new affected source crude oil and if the annual average total organic HAP (or,

meeting the capacity criteria specified true vapor pressure of the total Table upon approval, TOC) by at

in table 2 of this subpart, items 1 1 organic HAP in the stored organic least 95 weight-percent

through 5. liquid is =76.6 kilopascals or, as an option, to an

(11.1 psia). exhaust concentration less

than or equal to 20 ppmv,

on a dry basis corrected

to 3 percent oxygen for

combustion devices using

supplemental combustion

air, by venting emissions

through a closed vent

system to any combination

of control devices meeting

the applicable

requirements of 40 CFR

part 63, subpart SS; OR

ii. Comply with the work

practice standards

specified in table 4 to

this subpart, item 2.a,

for tanks storing the

liquids described in that

table.7. A transfer rack at an existing a. The total table 1 organic HAP content i. For all such loading

facility where the total actual annual of the organic liquid being loaded arms at the rack, reduce

facility-level organic liquid loading through one or more of the transfer emissions of total organic

volume through transfer racks is equal rack's arms is at least 98 percent by HAP (or, upon approval,

to or greater than 800,000 gallons and weight and is being loaded into a TOC) from the loading of

less than 10 million gallons. transport vehicle. organic liquids either by

venting the emissions that

occur during loading

through a closed vent

system to any combination

of control devices meeting

the applicable

requirements of 40 CFR

part 63, subpart SS,

achieving at least 98

weight-percent HAP

reduction, OR, as an

option, to an exhaust

concentration less than or

equal to 20 ppmv, on a dry

basis corrected to 3

percent oxygen for

combustion devices using

supplemental combustion

air; OR

ii. During the loading of

organic liquids, comply

with the work practice

standards specified in

item 3 of table 4 to this

subpart.8. A transfer rack at an existing a. One or more of the transfer rack's i. See the requirements in

facility where the total actual annual arms is loading an organic liquid into items 7.a.i and 7.a.ii of

facility-level organic liquid loading a transport vehicle. this table.

volume through transfer racks is =10 million gallons.9. A transfer rack at a new facility a. The total Table 1 organic HAP content i. See the requirements in

where the total actual annual facility- of the organic liquid being loaded items 7.a.i and 7.a.ii of

level organic liquid loading volume through one or more of the transfer this table.

through transfer racks is less than rack's arms is at least 25 percent by

800,000 gallons weight and is being loaded into a

transport vehicle

b. One or more of the transfer rack's i. For all such loading

arms is filling a container with a arms at the rack during

capacity equal to or greater than 55 the loading of organic

gallons liquids, comply with the

provisions of Sec. Sec.

63.924 through 63.927 of

40 CFR part 63, Subpart

PP--National Emission

Standards for Containers,

Container Level 3

controls; OR

ii. During the loading of

organic liquids, comply

with the work practice

standards specified in

item 3.a of Table 4 to

this subpart.10. A transfer rack at a new facility a. One or more of the transfer rack's i. See the requirements in

where the total actual annual facility- arms is loading an organic liquid into items 7.a.i and 7.a.ii of

level organic liquid loading volume a transport vehicle. this table.

through transfer racks is equal to or

greater than 800,000 gallons.

b. One or more of the transfer rack's i. For all such loading

arms is filling a container with a arms at the rack during

capacity equal to or greater than 55 the loading of organic

gallons. liquids, comply with the

provisions of Sec. Sec.

63.924 through 63.927 of

40 CFR part 63, Subpart

PP--National Emission

Standards for Containers,

Container Level 3

controls; OR

ii. During the loading of

organic liquids, comply

with the work practice

standards specified in

item 3.a of table 4 to

this subpart.---------------------------------------------------------------------------------------------------------------- [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42913, July 28, 2006; 73 FR 21830, Apr. 23, 2008]

Sec. Table 3 to Subpart EEEE of Part 63--Operating Limits--High

Throughput Transfer Racks

As stated in Sec. 63.2346(e), you must comply with the operating limits for existing, reconstructed, or new affected sources as follows: ------------------------------------------------------------------------

For each existing, each

reconstructed, and each new You must . . .

affected source using . . .------------------------------------------------------------------------1. A thermal oxidizer to Maintain the daily average fire box or

comply with an emission combustion zone temperature greater than

limit in table 2 to this or equal to the reference temperature

subpart. established during the design evaluation

or performance test that demonstrated

compliance with the emission limit.2. A catalytic oxidizer to a. Replace the existing catalyst bed

comply with an emission before the age of the bed exceeds the

limit in table 2 to this maximum allowable age established during

subpart. the design evaluation or performance

test that demonstrated compliance with

the emission limit; AND

b. Maintain the daily average temperature

at the inlet of the catalyst bed greater

than or equal to the reference

temperature established during the

design evaluation or performance test

that demonstrated compliance with the

emission limit; AND

c. Maintain the daily average temperature

difference across the catalyst bed

greater than or equal to the minimum

temperature difference established

during the design evaluation or

performance test that demonstrated

compliance with the emission limit.3. An absorber to comply with a. Maintain the daily average

an emission limit in table 2 concentration level of organic compounds

to this subpart. in the absorber exhaust less than or

equal to the reference concentration

established during the design evaluation

or performance test that demonstrated

compliance with the emission limit; OR

b. Maintain the daily average scrubbing

liquid temperature less than or equal to

the reference temperature established

during the design evaluation or

performance test that demonstrated

compliance with the emission limit; AND

Maintain the difference between the

specific gravities of the saturated and

fresh scrubbing fluids greater than or

equal to the difference established

during the design evaluation or

performance test that demonstrated

compliance with the emission limit.4. A condenser to comply with a. Maintain the daily average

an emission limit in table 2 concentration level of organic compounds

to this subpart. at the condenser exit less than or equal

to the reference concentration

established during the design evaluation

or performance test that demonstrated

compliance with the emission limit; OR

b. Maintain the daily average condenser

exit temperature less than or equal to

the reference temperature established

during the design evaluation or

performance test that demonstrated

compliance with the emission limit.5. An adsorption system with a. Maintain the daily average

adsorbent regeneration to concentration level of organic compounds

comply with an emission in the adsorber exhaust less than or

limit in table 2 to this equal to the reference concentration

subpart. established during the design evaluation

or performance test that demonstrated

compliance with the emission limit; OR

b. Maintain the total regeneration stream

mass flow during the adsorption bed

regeneration cycle greater than or equal

to the reference stream mass flow

established during the design evaluation

or performance test that demonstrated

compliance with the emission limit; AND

Before the adsorption cycle commences,

achieve and maintain the temperature of

the adsorption bed after regeneration

less than or equal to the reference

temperature established during the

design evaluation or performance test

that demonstrated compliance with the

emission limit; AND

Achieve a pressure reduction during each

adsorption bed regeneration cycle

greater than or equal to the pressure

reduction established during the design

evaluation or performance test that

demonstrated compliance with the

emission limit.6. An adsorption system a. Maintain the daily average

without adsorbent concentration level of organic compounds

regeneration to comply with in the adsorber exhaust less than or

an emission limit in table 2 equal to the reference concentration

to this subpart. established during the design evaluation

or performance test that demonstrated

compliance with the emission limit; OR

b. Replace the existing adsorbent in each

segment of the bed with an adsorbent

that meets the replacement

specifications established during the

design evaluation or performance test

before the age of the adsorbent exceeds

the maximum allowable age established

during the design evaluation or

performance test that demonstrated

compliance with the emission limit; AND

Maintain the temperature of the

adsorption bed less than or equal to the

reference temperature established during

the design evaluation or performance

test that demonstrated compliance with

the emission limit.7. A flare to comply with an a. Comply with the equipment and

emission limit in table 2 to operating requirements in Sec.

this subpart. 63.987(a); AND

b. Conduct an initial flare compliance

assessment in accordance with Sec.

63.987(b); AND

c. Install and operate monitoring

equipment as specified in Sec.

63.987(c).8. Another type of control Submit a monitoring plan as specified in

device to comply with an Sec. Sec. 63.995(c) and 63.2366(b),

emission limit in table 2 to and monitor the control device in

this subpart. accordance with that plan.------------------------------------------------------------------------ [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42914, July 28, 2006]

Sec. Table 4 to Subpart EEEE of Part 63--Work Practice Standards

As stated in Sec. 63.2346, you may elect to comply with one of the work practice standards for existing, reconstructed, or new affected sources in the following table. If you elect to do so, . . . ------------------------------------------------------------------------

For each . . . You must . . .------------------------------------------------------------------------1. Storage tank at an existing, a. Comply with the requirements

reconstructed, or new affected source of 40 CFR part 63, subpart WW

meeting any set of tank capacity and (control level 2), if you

organic HAP vapor pressure criteria elect to meet 40 CFR part 63,

specified in table 2 to this subpart, subpart WW (control level 2)

items 1 through 5. requirements as an alternative

to the emission limit in table

2 to this subpart, items 1

through 5; OR

b. Comply with the requirements

of Sec. 63.984 for routing

emissions to a fuel gas system

or back to a process; OR

c. Comply with the requirements

of Sec. 63.2346(a)(4) for

vapor balancing emissions to

the transport vehicle from

which the storage tank is

filled.2. Storage tank at an existing, a. Comply with the requirements

reconstructed, or new affected source of Sec. 63.984 for routing

meeting any set of tank capacity and emissions to a fuel gas system

organic HAP vapor pressure criteria or back to a process; OR

specified in table 2 to this subpart, b. Comply with the requirements

item 6. of Sec. 63.2346(a)(4) for

vapor balancing emissions to

the transport vehicle from

which the storage tank is

filled.3. Transfer rack subject to control a. If the option of a vapor

based on the criteria specified in balancing system is selected,

table 2 to this subpart, items 7 install and, during the

through 10, at an existing, loading of organic liquids,

reconstructed, or new affected source. operate a system that meets

the requirements in table 7 to

this subpart, item 3.b.i and

item 3.b.ii, as applicable; OR

b. Comply with the requirements

of Sec. 63.984 during the

loading of organic liquids,

for routing emissions to a

fuel gas system or back to a

process.4. Pump, valve, and sampling connection Comply with the requirements

that operates in organic liquids for pumps, valves, and

service at least 300 hours per year at sampling connections in 40 CFR

an existing, reconstructed, or new part 63, subpart TT (control

affected source. level 1), subpart UU (control

level 2), or subpart H.5. Transport vehicles equipped with Follow the steps in 40 CFR

vapor collection equipment that are 60.502(e) to ensure that

loaded at transfer racks that are organic liquids are loaded

subject to control based on the only into vapor-tight

criteria specified in table 2 to this transport vehicles, and comply

subpart, items 7 through 10. with the provisions in 40 CFR

60.502(f), (g), (h), and (i),

except substitute the term

transport vehicle at each

occurrence of tank truck or

gasoline tank truck in those

paragraphs.6. Transport vehicles equipped without Ensure that organic liquids are

vapor collection equipment that are loaded only into transport

loaded at transfer racks that are vehicles that have a current

subject to control based on the certification in accordance

criteria specified in table 2 to this with the U.S. DOT pressure

subpart, items 7 through 10. test requirements in 49 CFR

180 (cargo tanks) or 49 CFR

173.31 (tank cars).------------------------------------------------------------------------ [71 FR 42915, July 28, 2006]

Sec. Table 5 to Subpart EEEE of Part 63--Requirements for Performance

Tests and Design Evaluations

As stated in Sec. Sec. 63.2354(a) and 63.2362, you must comply with the requirements for performance tests and design evaluations for existing, reconstructed, or new affected sources as follows: --------------------------------------------------------------------------------------------------------------------------------------------------------

According to the

For . . . You must conduct . . . According to . . . Using . . . To determine . . . following

(1) EPA Method 1 or (A) Sampling port (i) Sampling sites

reconstructed, and each new to determine the 63.985(b)(1)(ii), 1A in appendix A-1 locations and the must be located at

affected source using a nonflare organic HAP (or, upon Sec. 63.988(b), of 40 CFR part 60, required number of the inlet and outlet

control device to comply with an approval, TOC) Sec. 63.990(b), or as appropriate. traverse points. of each control

emission limit in Table 2 to this control efficiency of Sec. 63.995(b). device if complying

subpart, items 1 through 10. each nonflare control with the control

device, OR the efficiency

exhaust concentration requirement or at

of each combustion the outlet of the

device; OR. control device if

complying with the

exhaust

concentration

requirement; AND

(ii) the outlet

sampling site must

be located at each

control device prior

to any releases to

the atmosphere.

(2) EPA Method 2, 2A, (A) Stack gas See the requirements

2C, 2D, or 2F in velocity and in items

(1)(A)(i) and

CFR part 60, or EPA (ii) of this table.

Method 2G in

appendix A-2 of 40

CFR part 60, as

appropriate.

(3) EPA Method 3 or (A) Concentration of See the requirements

3B in appendix A-2 CO2 and O2 and dry in items

(1)(A)(i) and

as appropriate. the stack gas. (ii) of this table.

(4) EPA Method 4 in (A) Moisture content See the requirements

appendix A-3 of 40 of the stack gas. in items

(1)(A)(i) and

(ii) of this table.

(5) EPA Method 18 in (A) Total organic HAP (i) The organic HAP

appendix A-6 of 40 (or, upon approval, used for the

CFR part 60, or EPA TOC), or calibration gas for

Method 25 or 25A in formaldehyde EPA Method 25A in

appendix A-7 of 40 emissions. appendix A-7 of 40

CFR part 60, as CFR part 60 must be

appropriate, or EPA the single organic

Method 316 in HAP representing the

appendix A of 40 CFR largest percent by

part 63 for volume of emissions;

measuring form- AND

aldehyde. (ii) During the

performance test,

you must establish

the operating

parameter limits

within which total

organic HAP (or,

upon approval, TOC)

emissions are

reduced by the

required weight-

percent or, as an

option for nonflare

combustion devices,

to 20 ppmv exhaust

concentration.

b. A design evaluation Sec. 63.985(b)(1)(i) ..................... ..................... During a design

(for nonflare control evaluation, you must

devices) to determine establish the

the organic HAP (or, operating parameter

upon approval, TOC) limits within which

control efficiency of total organic HAP,

each nonflare control (or, upon approval,

device, or the TOC) emissions are

exhaust concentration reduced by at least

of each combustion 95 weight-percent

control device. for storage tanks or

98 weight-percent

for transfer racks,

or, as an option for

nonflare combustion

devices, to 20 ppmv

exhaust

concentration.2. Each transport vehicle that you A performance test to ...................... EPA Method 27 in Vapor tightness...... The pressure change

own that is equipped with vapor determine the vapor appendix A of 40 CFR in the tank must be

collection equipment and is loaded tightness of the tank part 60. no more than 250

with organic liquids at a transfer and then repair as pascals (1 inch of

rack that is subject to control needed until it water) in 5 minutes

based on the criteria specified in passes the test.. after it is

table 2 to this subpart, items 7 pressurized to 4,500

through 10, at an existing, pascals (18 inches

reconstructed, or new affected of water).

source.-------------------------------------------------------------------------------------------------------------------------------------------------------- [71 FR 42916, July 28, 2006, as amended at 73 FR 21831, Apr. 23, 2008]

Sec. Table 6 to Subpart EEEE of Part 63--Initial Compliance With

Emission Limits

As stated in Sec. Sec. 63.2370(a) and 63.2382(b), you must show initial compliance with the emission limits for existing, reconstructed, or new affected sources as follows: ------------------------------------------------------------------------

You have

For each . . . For the following demonstrated initial

emission limit . . . compliance if . . .------------------------------------------------------------------------1. Storage tank at an Reduce total organic Total organic HAP

existing, reconstructed, or HAP (or, upon (or, upon approval,

new affected source meeting approval, TOC) TOC) emissions,

any set of tank capacity emissions by at based on the

and liquid organic HAP least 95 weight- results of the

vapor pressure criteria percent, or as an performance testing

specified in Table 2 to option for nonflare or design

this subpart, items 1 combustion devices evaluation

through 6. to an exhaust specified in Table

concentration of 5 to this subpart,

<=20 ppmv. item 1.a or 1.b,

respectively, are

reduced by at least

95 weight-percent

or as an option for

nonflare combustion

devices to an

exhaust

concentration <=20

ppmv.

2. Transfer rack that is Reduce total organic Total organic HAP

subject to control based on HAP (or, upon (or, upon approval,

the criteria specified in approval, TOC) TOC) emissions from

table 2 to this subpart, emissions from the the loading of

items 7 through 10, at an loading of organic organic liquids,

existing, reconstructed, or liquids by at least based on the

new affected source. 98 weight-percent, results of the

or as an option for performance testing

nonflare combustion or design

devices to an evaluation

exhaust specified in table

concentration of 5 to this subpart,

<=20 ppmv. item 1.a or 1.b,

respectively, are

reduced by at least

98 weight-percent

or as an option for

nonflare combustion

devices to an

exhaust

concentration of

<=20 ppmv.------------------------------------------------------------------------ [71 FR 42918, July 28, 2006, as amended at 73 FR 21832, Apr. 23, 2008]

Sec. Table 7 to Subpart EEEE of Part 63--Initial Compliance With Work

Practice Standards ------------------------------------------------------------------------

You have

For each . . . If you . . . demonstrated initial

compliance if . . .------------------------------------------------------------------------1. Storage tank at an a. Install a i. After emptying

existing affected source floating roof or and degassing, you

meeting either set of tank equivalent control visually inspect

capacity and liquid organic that meets the each internal

HAP vapor pressure criteria requirements in floating roof

specified in Table 2 to Table 4 to this before the

this subpart, items 1 or 2. subpart, item 1.a. refilling of the

storage tank and

perform seal gap

inspections of the

primary and

secondary rim seals

of each external

floating roof

within 90 days

after the refilling

of the storage

tank.

b. Route emissions i. You meet the

to a fuel gas requirements in

system or back to a Sec. 63.984(b)

process. and submit the

statement of

connection required

by Sec.

63.984(c).

c. Install and, i. You meet the

during the filling requirements in

of the storage tank Sec.

with organic 63.2346(a)(4).

liquids, operate a

vapor balancing

system.2. Storage tank at a a. Install a i. You visually

reconstructed or new floating roof or inspect each

affected source meeting any equivalent control internal floating

set of tank capacity and that meets the roof before the

liquid organic HAP vapor requirements in initial filling of

pressure criteria specified Table 4 to this the storage tank,

in Table 2 to this subpart, subpart, item 1.a. and perform seal

items 3 through 5. gap inspections of

the primary and

secondary rim seals

of each external

floating roof

within 90 days

after the initial

filling of the

storage tank.

b. Route emissions i. See item 1.b.i of

to a fuel gas this table.

system or back to a

process.

c. Install and, i. See item 1.c.i of

during the filling this table.

of the storage tank

with organic

liquids, operate a

vapor balancing

system.3. Transfer rack that is a. Load organic i. You comply with

subject to control based on liquids only into the provisions

the criteria specified in transport vehicles specified in table

table 2 to this subpart, having current 4 to this subpart,

items 7 through 10, at an vapor tightness item 5 or item 6,

existing, reconstructed, or certification as as applicable.

new affected source. described in table

4 to this subpart,

item 5 and item 6.

b. Install and, i. You design and

during the loading operate the vapor

of organic liquids, balancing system to

operate a vapor route organic HAP

balancing system. vapors displaced

from loading of

organic liquids

into transport

vehicles to the

storage tank from

which the liquid

being loaded

originated or to

another storage

tank connected to a

common header.

ii. You design and

operate the vapor

balancing system to

route organic HAP

vapors displaced

from loading of

organic liquids

into containers

directly (e.g., no

intervening tank or

containment area

such as a room) to

the storage tank

from which the

liquid being loaded

originated or to

another storage

tank connected to a

common header.

c. Route emissions i. See item 1.b.i of

to a fuel gas this table.

system or back to a

process.

4. Equipment leak component, a. Carry out a leak i. You specify which

as defined in Sec. detection and one of the control

63.2406, that operates in repair program or programs listed in

organic liquids service =300 hours per year according to one of subpart you have

at an existing, the subparts listed selected, OR

reconstructed, or new in table 4 to this ii. Provide written

affected source. subpart, item 4.a. specifications for

your equivalent

control approach.------------------------------------------------------------------------ [71 FR 42918, July 28, 2006, as amended at 73 FR 21833, Apr. 23, 2008]

Sec. Table 8 to Subpart EEEE of Part 63--Continuous Compliance With

Emission Limits

As stated in Sec. Sec. 63.2378(a) and (b) and 63.2390(b), you must show continuous compliance with the emission limits for existing, reconstructed, or new affected sources according to the following table: ------------------------------------------------------------------------

You must demonstrate

For the following continuous

For each . . . emission limit . . . compliance by . . .

------------------------------------------------------------------------1. Storage tank at an a. Reduce total i. Performing CMS

existing, reconstructed, or organic HAP (or, monitoring and

new affected source meeting upon approval, TOC) collecting data

any set of tank capacity emissions from the according to Sec.

and liquid organic HAP closed vent system Sec. 63.2366,

vapor pressure criteria and control device 63.2374, and

specified in table 2 to by 95 weight- 63.2378; AND

this subpart, items 1 percent or greater, ii. Maintaining the

through 6. or as an option to operating limits

20 ppmv or less of established during

total organic HAP the design

(or, upon approval, evaluation or

TOC) in the exhaust performance test

of combustion that demonstrated

devices. compliance with the

emission limit.2. Transfer rack that is a. Reduce total i. Performing CMS

subject to control based on organic HAP (or, monitoring and

the criteria specified in upon approval, TOC) collecting data

table 2 to this subpart, emissions during according to Sec.

items 7 through 10, at an the loading of Sec. 63.2366,

existing, reconstructed, or organic liquids 63.2374, and

new affected source. from the closed 63.2378 during the

vent system and loading of organic

control device by liquids; AND

98 weight-percent ii. Maintaining the

or greater, or as operating limits

an option to 20 established during

ppmv or less of the design

total organic HAP evaluation or

(or, upon approval, performance test

TOC) in the exhaust that demonstrated

of combustion compliance with the

devices. emission limit

during the loading

of organic liquids.------------------------------------------------------------------------ [71 FR 42919, July 28, 2006]

Sec. Table 9 to Subpart EEEE of Part 63--Continuous Compliance With

Operating Limits--High Throughput Transfer Racks

As stated in Sec. Sec. 63.2378(a) and (b) and 63.2390(b), you must show continuous compliance with the operating limits for existing, reconstructed, or new affected sources according to the following table: ----------------------------------------------------------------------------------------------------------------

You must demonstrate

For each existing, reconstructed, and For the following operating limit . . . continuous compliance by .

each new affected source using . . . . .----------------------------------------------------------------------------------------------------------------1. A thermal oxidizer to comply with an a. Maintain the daily average fire box i. Continuously monitoring

emission limit in table 2 to this or combustion zone, as applicable, and recording fire box or

subpart. temperature greater than or equal to combustion zone, as

the reference temperature established applicable, temperature

during the design evaluation or every 15 minutes and

performance test that demonstrated maintaining the daily

compliance with the emission limit. average fire box

temperature greater than

or equal to the reference

temperature established

during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

ii. Keeping the applicable

records required in Sec.

63.998.2. A catalytic oxidizer to comply with an a. Replace the existing catalyst bed i. Replacing the existing

emission limit in table 2 to this before the age of the bed exceeds the catalyst bed before the

subpart. maximum allowable age established age of the bed exceeds the

during the design evaluation or maximum allowable age

performance test that demonstrated established during the

compliance with the emission limit; AND design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Maintain the daily average i. Continuously monitoring

temperature at the inlet of the and recording the

catalyst bed greater than or equal to temperature at the inlet

the reference temperature established of the catalyst bed at

during the design evaluation or least every 15 minutes and

performance test that demonstrated maintaining the daily

compliance with the emission limit; AND average temperature at the

inlet of the catalyst bed

greater than or equal to

the reference temperature

established during the

design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

ii. Keeping the applicable

records required in Sec.

63.998.

c. Maintain the daily average i. Continuously monitoring

temperature difference across the and recording the

catalyst bed greater than or equal to temperature at the outlet

the minimum temperature difference of the catalyst bed every

established during the design 15 minutes and maintaining

evaluation or performance test that the daily average

demonstrated compliance with the temperature difference

emission limit. across the catalyst bed

greater than or equal to

the minimum temperature

difference established

during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

ii. Keeping the applicable

records required in Sec.

63.998.3. An absorber to comply with an emission a. Maintain the daily average i. Continuously monitoring

limit in table 2 to this subpart. concentration level of organic the organic concentration

compounds in the absorber exhaust less in the absorber exhaust

than or equal to the reference and maintaining the daily

concentration established during the average concentration less

design evaluation or performance test than or equal to the

that demonstrated compliance with the reference concentration

emission limit; OR established during the

design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Maintain the daily average scrubbing i. Continuously monitoring

liquid temperature less than or equal the scrubbing liquid

to the reference temperature temperature and

established during the design maintaining the daily

evaluation or performance test that average temperature less

demonstrated compliance with the than or equal to the

emission limit; AND reference temperature

Maintain the difference between the established during the

specific gravities of the saturated and design evaluation or

fresh scrubbing fluids greater than or performance test that

equal to the difference established demonstrated compliance

during the design evaluation or with the emission limit;

performance test that demonstrated AND

compliance with the emission limit. ii. Maintaining the

difference between the

specific gravities greater

than or equal to the

difference established

during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

iii. Keeping the applicable

records required in Sec.

63.998.4. A condenser to comply with an emission a. Maintain the daily average i. Continuously monitoring

limit in table 2 to this subpart. concentration level of organic the organic concentration

compounds at the exit of the condenser at the condenser exit and

less than or equal to the reference maintaining the daily

concentration established during the average concentration less

design evaluation or performance test than or equal to the

that demonstrated compliance with the reference concentration

emission limit; OR established during the

design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Maintain the daily average condenser i. Continuously monitoring

exit temperature less than or equal to and recording the

the reference temperature established temperature at the exit of

during the design evaluation or the condenser at least

performance test that demonstrated every 15 minutes and

compliance with the emission limit. maintaining the daily

average temperature less

than or equal to the

reference temperature

established during the

design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

ii. Keeping the applicable

records required in Sec.

63.998.

5. An adsorption system with adsorbent a. Maintain the daily average i. Continuously monitoring

regeneration to comply with an emission concentration level of organic the daily average organic

limit in table 2 to this subpart. compounds in the adsorber exhaust less concentration in the

than or equal to the reference adsorber exhaust and

concentration established during the maintaining the

design evaluation or performance test concentration less than or

that demonstrated compliance with the equal to the reference

emission limit; OR concentration established

during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Maintain the total regeneration i. Maintaining the total

stream mass flow during the adsorption regeneration stream mass

bed regeneration cycle greater than or flow during the adsorption

equal to the reference stream mass flow bed regeneration cycle

established during the design greater than or equal to

evaluation or performance test that the reference stream mass

demonstrated compliance with the flow established during

emission limit; AND the design evaluation or

Before the adsorption cycle commences, performance test that

achieve and maintain the temperature of demonstrated compliance

the adsorption bed after regeneration with the emission limit;

less than or equal to the reference AND

temperature established during the ii. Maintaining the

design evaluation or performance test; temperature of the

AND adsorption bed after

Achieve greater than or equal to the regeneration less than or

pressure reduction during the equal to the reference

adsorption bed regeneration cycle temperature established

established during the design during the design

evaluation or performance test that evaluation or performance

demonstrated compliance with the test that demonstrated

emission limit. compliance with the

emission limit; AND

iii. Achieving greater than

or equal to the pressure

reduction during the

regeneration cycle

established during the

design evaluation or

performance test that

demonstrated compliance

with the emission limit;

AND

iv. Keeping the applicable

records required in Sec.

63.998.6. An adsorption system without adsorbent a. Maintain the daily average i. Continuously monitoring

regeneration to comply with an emission concentration level of organic the organic concentration

limit in table 2 to this subpart. compounds in the adsorber exhaust less in the adsorber exhaust

than or equal to the reference and maintaining the

concentration established during the concentration less than or

design evaluation or performance test equal to the reference

that demonstrated compliance with the concentration established

emission limit; OR during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Replace the existing adsorbent in i. Replacing the existing

each segment of the bed before the age adsorbent in each segment

of the adsorbent exceeds the maximum of the bed with an

allowable age established during the adsorbent that meets the

design evaluation or performance test replacement specifications

that demonstrated compliance with the established during the

emission limit; AND design evaluation or

Maintain the temperature of the performance test before

adsorption bed less than or equal to the age of the adsorbent

the reference temperature established exceeds the maximum

during the design evaluation or allowable age established

performance test that demonstrated during the design

compliance with the emission limit. evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

ii. Maintaining the

temperature of the

adsorption bed less than

or equal to the reference

temperature established

during the design

evaluation or performance

test that demonstrated

compliance with the

emission limit; AND

iii. Keeping the applicable

records required in Sec.

63.998.7. A flare to comply with an emission a. Maintain a pilot flame in the flare i. Continuously operating a

limit in table 2 to this subpart. at all times that vapors may be vented device that detects the

to the flare (Sec. 63.11(b)(5)); AND presence of the pilot

flame; AND

ii. Keeping the applicable

records required in Sec.

63.998.

b. Maintain a flare flame at all times i. Maintaining a flare

that vapors are being vented to the flame at all times that

flare (Sec. 63.11(b)(5)); AND vapors are being vented to

the flare; AND

ii. Keeping the applicable

records required in Sec.

63.998.

c. Operate the flare with no visible i. Operating the flare with

emissions, except for up to 5 minutes no visible emissions

in any 2 consecutive hours (Sec. exceeding the amount

63.11(b)(4)); AND EITHER allowed; AND

ii. Keeping the applicable

records required in Sec.

63.998.

d.1. Operate the flare with an exit i. Operating the flare

velocity that is within the applicable within the applicable exit

limits in Sec. 63.11(b)(7) and (8) velocity limits; AND

and with a net heating value of the gas ii. Operating the flare

being combusted greater than the with the gas heating value

applicable minimum value in Sec. greater than the

63.11(b)(6)(ii); OR applicable minimum value;

AND

iii. Keeping the applicable

records required in Sec.

63.998.

d.2. Adhere to the requirements in Sec. i. Operating the flare

63.11(b)(6)(i). within the applicable

limits in 63.11(b)(6)(i);

AND

ii. Keeping the applicable

records required in Sec.

63.998.8. Another type of control device to Submit a monitoring plan as specified in Submitting a monitoring

comply with an emission limit in table 2 Sec. Sec. 63.995(c) and 63.2366(c), plan and monitoring the

to this subpart. and monitor the control device in control device according

accordance with that plan. to that plan.---------------------------------------------------------------------------------------------------------------- [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42919, July 28, 2006]

Sec. Table 10 to Subpart EEEE of Part 63--Continuous Compliance With

Work Practice Standards

As stated in Sec. Sec. 63.2378(a) and (b) and 63.2386(c)(6), you must show continuous compliance with the work practice standards for existing, reconstructed, or new affected sources according to the following table: ----------------------------------------------------------------------------------------------------------------

You must demonstrate

For each . . . For the following standard . . . continuous compliance by .

. .----------------------------------------------------------------------------------------------------------------1. Internal floating roof (IFR) storage a. Install a floating roof designed and i. Visually inspecting the

tank at an existing, reconstructed, or operated according to the applicable floating roof deck, deck

new affected source meeting any set of specifications in Sec. 63.1063(a) and fittings, and rim seals of

tank capacity, and vapor pressure (b). each IFR once per year

criteria specified in table 2 to this (Sec. 63.1063(d)(2));

subpart, items 1 through 5. AND

ii. Visually inspecting the

floating roof deck, deck

fittings, and rim seals of

each IFR either each time

the storage tank is

completely emptied and

degassed or every 10

years, whichever occurs

first (Sec.

63.1063(c)(1), (d)(1), and

(e)); AND

iii. Keeping the tank

records required in Sec.

63.1065.2. External floating roof (EFR) storage a. Install a floating roof designed and i. Visually inspecting the

tank at an existing, reconstructed, or operated according to the applicable floating roof deck, deck

new affected source meeting any set of specifications in Sec. 63.1063(a) and fittings, and rim seals of

tank capacity and vapor pressure (b). each EFR either each time

criteria specified in table 2 to this the storage tank is

subpart, items 1 through 5. completely emptied and

degassed or every 10

years, whichever occurs

first (Sec.

63.1063(c)(2), (d), and

(e)); AND

ii. Performing seal gap

measurements on the

secondary seal of each EFR

at least once every year,

and on the primary seal of

each EFR at least every 5

years (Sec.

63.1063(c)(2), (d), and

(e)); AND

iii. Keeping the tank

records required in Sec.

63.1065.3. IFR or EFR tank at an existing, a. Repair the conditions causing storage i. Repairing conditions

reconstructed, or new affected source tank inspection failures (Sec. causing inspection

meeting any set of tank capacity and 63.1063(e)). failures: before refilling

vapor pressure criteria specified in the storage tank with

table 2 to this subpart, items 1 through organic liquid, or within

5. 45 days (or up to 105 days

with extensions) for a

tank containing organic

liquid; AND

ii. Keeping the tank

records required in Sec.

63.1065(b).

4. Transfer rack that is subject to a. Ensure that organic liquids are i. Ensuring that organic

control based on the criteria specified loaded into transport vehicles in liquids are loaded into

in table 2 to this subpart, items 7 accordance with the requirements in transport vehicles in

through 10, at an existing, table 4 to this subpart, items 5 or 6, accordance with the

reconstructed, or new affected source. as applicable. requirements in table 4 to

this subpart, items 5 or

6, as applicable.

b. Install and, during the loading of i. Monitoring each

organic liquids, operate a vapor potential source of vapor

balancing system. leakage in the system

quarterly during the

loading of a transport

vehicle or the filling of

a container using the

methods and procedures

described in the rule

requirements selected for

the work practice standard

for equipment leak

components as specified in

table 4 to this subpart,

item 4. An instrument

reading of 500 ppmv

defines a leak. Repair of

leaks is performed

according to the repair

requirements specified in

your selected equipment

leak standards.

c. Route emissions to a fuel gas system i. Continuing to meet the

or back to a process. requirements specified in

Sec. 63.984(b).5. Equipment leak component, as defined a. Comply with the requirements of 40 i. Carrying out a leak

in Sec. 63.2406, that operates in CFR part 63, subpart TT, UU, or H. detection and repair

organic liquids service at least 300 program in accordance with

hours per year. the subpart selected from

the list in item 5.a of

this table.6. Storage tank at an existing, a. Route emissions to a fuel gas system i. Continuing to meet the

reconstructed, or new affected source or back to the process. requirements specified in

meeting any of the tank capacity and Sec. 63.984(b).

vapor pressure criteria specified in

table 2 to this subpart, items 1 through

6.

b. Install and, during the filling of i. Except for pressure

the storage tank with organic liquids, relief devices, monitoring

operate a vapor balancing system. each potential source of

vapor leakage in the

system, including, but not

limited to pumps, valves,

and sampling connections,

quarterly during the

loading of a storage tank

using the methods and

procedures described in

the rule requirements

selected for the work

practice standard for

equipment leak components

as specified in Table 4 to

this subpart, item 4. An

instrument reading of 500

ppmv defines a leak.

Repair of leaks is

performed according to the

repair requirements

specified in your selected

equipment leak standards.

For pressure relief

devices, comply with Sec.

63.2346(a)(4)(v). If no

loading of a storage tank

occurs during a quarter,

then monitoring of the

vapor balancing system is

not required.---------------------------------------------------------------------------------------------------------------- [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 42922, July 28, 2006; 73 FR 40982, July 17, 2008]

Sec. Table 11 to Subpart EEEE of Part 63--Requirements for Reports

As stated in Sec. 63.2386(a), (b), and (f), you must submit compliance reports and startup, shutdown, and malfunction reports according to the following table: ------------------------------------------------------------------------

The report must You must submit the

You must submit a(n) . . . contain . . . report . . .------------------------------------------------------------------------1. Compliance report or a. The information Semiannually, and it

Periodic Report. specified in Sec. must be postmarked

63.2386(c), (d), by January 31 or

(e). If you had a July 31, in

SSM during the accordance with

reporting period Sec. 63.2386(b).

and you took

actions consistent

with your SSM plan,

the report must

also include the

information in Sec.

63.10(d)(5)(i);

AND

b. The information See the submission

required by 40 CFR requirement in item

part 63, subpart 1.a of this table.

TT, UU, or H, as

applicable, for

pumps, valves, and

sampling

connections; AND

c. The information See the submission

required by Sec. requirement in item

63.999(c); AND 1.a of this table.

d. The information See the submission

specified in Sec. requirement in item

63.1066(b) 1.a. of this table.

including:

Notification of

inspection,

inspection results,

requests for

alternate devices,

and requests for

extensions, as

applicable.2. Immediate SSM report if a. The information i. By letter within

you had a SSM that resulted required in Sec. 7 working days

in an applicable emission 63.10(d)(5)(ii). after the end of

standard in the relevant the event unless

standard being exceeded, you have made

and you took an action that alternative

was not consistent with arrangements with

your SSM plan. the permitting

authority (Sec.

63.10(d)(5)(ii)).------------------------------------------------------------------------ [71 FR 42923, July 28, 2006]

Sec. Table 12 to Subpart EEEE of Part 63--Applicability of General

Provisions to Subpart EEEE

As stated in Sec. Sec. 63.2382 and 63.2398, you must comply with the applicable General Provisions requirements as follows: ----------------------------------------------------------------------------------------------------------------

Applies to subpart

Citation Subject Brief description EEEE----------------------------------------------------------------------------------------------------------------Sec. 63.1........................ Applicability......... Initial applicability Yes.

determination;

Applicability after

standard established;

Permit requirements;

Extensions, Notifications.Sec. 63.2........................ Definitions........... Definitions for part 63 Yes.

standards.Sec. 63.3........................ Units and Units and abbreviations for Yes.

Abbreviations. part 63 standards.Sec. 63.4........................ Prohibited Activities Prohibited activities; Yes.

and Circumvention. Circumvention,

Severability.Sec. 63.5........................ Construction/ Applicability; Yes.

Reconstruction. Applications; Approvals.Sec. 63.6(a)..................... Compliance with GP apply unless compliance Yes.

Standards/O&M; extension; GP apply to

Applicability. area sources that become

major.Sec. 63.6(b)(1)-(4).............. Compliance Dates for Standards apply at Yes.

New and Reconstructed effective date; 3 years

Sources. after effective date; upon

startup; 10 years after

construction or

reconstruction commences

for section 112(f).Sec. 63.6(b)(5).................. Notification.......... Must notify if commenced Yes.

construction or

reconstruction after

proposal.Sec. 63.6(b)(6).................. [Reserved].Sec. 63.6(b)(7).................. Compliance Dates for Area sources that become Yes.

New and Reconstructed major must comply with

Area Sources That major source standards

Become Major. immediately upon becoming

major, regardless of

whether required to comply

when they were an area

source.Sec. 63.6(c)(1)-(2).............. Compliance Dates for Comply according to date in Yes.

Existing Sources. this subpart, which must

be no later than 3 years

after effective date; for

section 112(f) standards,

comply within 90 days of

effective date unless

compliance extension.Sec. 63.6(c)(3)-(4).............. [Reserved].Sec. 63.6(c)(5).................. Compliance Dates for Area sources that become Yes.

Existing Area Sources major must comply with

That Become Major. major source standards by

date indicated in this

subpart or by equivalent

time period (e.g., 3

years).Sec. 63.6(d)..................... [Reserved].Sec. 63.6(e)(1).................. Operation & Operate to minimize Yes.

Maintenance. emissions at all times;

correct malfunctions as

soon as practicable; and

operation and maintenance

requirements independently

enforceable; information

Administrator will use to

determine if operation and

maintenance requirements

were met.Sec. 63.6(e)(2).................. [Reserved].

(1) the

content of SSM plan; 2-day reporting

actions during SSM. requirement in

paragraph Sec.

63.6(e)(3)(iv) does

not apply and (2)

Sec. 63.6(e)(3)

does not apply to

emissions sources not

requiring control.Sec. 63.6(f)(1).................. Compliance Except You must comply with Yes.

During SSM. emission standards at all

times except during SSM.Sec. 63.6(f)(2)-(3).............. Methods for Compliance based on Yes.

Determining performance test,

Compliance. operation and maintenance

plans, records, inspection.Sec. 63.6(g)(1)-(3).............. Alternative Standard.. Procedures for getting an Yes.

alternative standard.Sec. 63.6(h)..................... Opacity/Visible Requirements for compliance No; except as it

Emission Standards. with opacity and visible applies to flares for

emission standards. which Method 22

observations are

required as part of a

flare compliance

assessment.Sec. 63.6(i)(1)-(14)............. Compliance Extension.. Procedures and criteria for Yes.

Administrator to grant

compliance extension.Sec. 63.6(j)..................... Presidential President may exempt any Yes.

Compliance Exemption. source from requirement to

comply with this subpart.Sec. 63.7(a)(2).................. Performance Test Dates Dates for conducting Yes.

initial performance

testing; must conduct 180

days after compliance date.Sec. 63.7(a)(3).................. Section 114 Authority. Adminsitrator may require a Yes.

performance test under CAA

section 114 at any time.Sec. 63.7(b)(1).................. Notification of Must notify Administrator Yes.

Performance Test. 60 days before the test.Sec. 63.7(b)(2).................. Notification of If you have to reschedule Yes.

Rescheduling. performance test, must

notify Administrator of

rescheduled date as soon

as practicable and without

delay.Sec. 63.7(c)..................... Quality Assurance (QA)/ Requirement to submit site- Yes.

Test Plan. specific test plan 60 days

before the test or on date

Administrator agrees with;

test plan approval

procedures; performance

audit requirements;

internal and external QA

procedures for testing.Sec. 63.7(d)..................... Testing Facilities.... Requirements for testing Yes.

facilities.Sec. 63.7(e)(1).................. Conditions for Performance tests must be Yes.

Conducting conducted under

Performance Tests. representative conditions;

cannot conduct performance

tests during SSM.Sec. 63.7(e)(2).................. Conditions for Must conduct according to Yes.

Conducting this subpart and EPA test

Performance Tests. methods unless

Administrator approves

alternative.Sec. 63.7(e)(3).................. Test Run Duration..... Must have three test runs Yes; however, for

of at least 1 hour each; transfer racks per

compliance is based on Sec. Sec.

arithmetic mean of three 63.987(b)(3)(i)(A)-(B

runs; conditions when data ) and

from an additional test 63.997(e)(1)(v)(A)-(B

run can be used. ) provide exceptions

to the requirement

for test runs to be

at least 1 hour each.Sec. 63.7(f)..................... Alternative Test Procedures by which Yes.

Method. Administrator can grant

approval to use an

intermediate or major

change, or alternative to

a test method.Sec. 63.7(g)..................... Performance Test Data Must include raw data in Yes; however,

Analysis. performance test report; performance test data

must submit performance is to be submitted

test data 60 days after with the Notification

end of test with the of Compliance Status

Notification of Compliance according to the

Status; keep data for 5 schedule specified in

years. Sec. 63.9(h)(1)-(6)

below.Sec. 63.7(h)..................... Waiver of Tests....... Procedures for Yes.

Administrator to waive

performance test.Sec. 63.8(a)(1).................. Applicability of Subject to all monitoring Yes.

Monitoring requirements in standard.

Requirements.Sec. 63.8(a)(2).................. Performance Performance Specifications Yes.

Specifications. in appendix B of 40 CFR

part 60 apply.

Sec. 63.8(a)(3).................. [Reserved].Sec. 63.8(a)(4).................. Monitoring of Flares.. Monitoring requirements for Yes; however,

flares in Sec. 63.11. monitoring

requirements in Sec.

63.987(c) also

apply.Sec. 63.8(b)(1).................. Monitoring............ Must conduct monitoring Yes.

according to standard

unless Administrator

approves alternative.Sec. 63.8(b)(2)-(3).............. Multiple Effluents and Specific requirements for Yes.

Multiple Monitoring installing monitoring

Systems. systems; must install on

each affected source or

after combined with

another affected source

before it is released to

the atmosphere provided

the monitoring is

sufficient to demonstrate

compliance with the

standard; if more than one

monitoring system on an

emission point, must

report all monitoring

system results, unless one

monitoring system is a

backup.Sec. 63.8(c)(1).................. Monitoring System Maintain monitoring system Yes.

Operation and in a manner consistent

Maintenance. with good air pollution

control practices.Sec. 63.8(c)(1)(i)-(iii)......... Routine and Keep parts for routine Yes.

Predictable SSM. repairs readily available;

reporting requirements for

SSM when action is

described in SSM plan..Sec. 63.8(c)(2)-(3).............. Monitoring System Must install to get Yes.

Installation. representative emission or

parameter measurements;

must verify operational

status before or at

performance test.Sec. 63.8(c)(4).................. CMS Requirements...... CMS must be operating Yes; however, COMS are

except during breakdown, not applicable.

out-of control, repair,

maintenance, and high-

level calibration drifts;

COMS must have a minimum

of one cycle of sampling

and analysis for each

successive 10-second

period and one cycle of

data recording for each

successive 6-minute

period; CEMS must have a

minimum of one cycle of

operation for each

successive 15-minute

period.Sec. 63.8(c)(5).................. COMS Minimum COMS minimum procedures.... No.

Procedures.Sec. 63.8(c)(6)-(8).............. CMS Requirements...... Zero and high level Yes, but only applies

calibration check for CEMS. 40 CFR part

requirements. Out-of- 63, subpart SS

control periods. provides requirements

for CPMS.Sec. 63.8(d)..................... CMS Quality Control... Requirements for CMS Yes, but only applies

quality control, including for CEMS. 40 CFR part

calibration, etc.; must 63, subpart SS

keep quality control plan provides requirements

on record for 5 years; for CPMS.

keep old versions for 5

years after revisions.Sec. 63.8(e)..................... CMS Performance Notification, performance Yes, but only applies

Evaluation. evaluation test plan, for CEMS.

reports.Sec. 63.8(f)(1)-(5).............. Alternative Monitoring Procedures for Yes, but 40 CFR part

Method. Administrator to approve 63, subpart SS also

alternative monitoring. provides procedures

for approval of CPMS.Sec. 63.8(f)(6).................. Alternative to Procedures for Yes.

Relative Accuracy Administrator to approve

Test. alternative relative

accuracy tests for CEMS.Sec. 63.8(g)..................... Data Reduction........ COMS 6-minute averages Yes; however, COMS are

calculated over at least not applicable.

36 evenly spaced data

points; CEMS 1 hour

averages computed over at

least 4 equally spaced

data points; data that

cannot be used in average.Sec. 63.9(a)..................... Notification Applicability and State Yes.

Requirements. delegation.Sec. 63.9(b)(1)-(2), (4)-(5)..... Initial Notifications. Submit notification within Yes.

120 days after effective

date; notification of

intent to construct/

reconstruct, notification

of commencement of

construction/

reconstruction,

notification of startup;

contents of each.Sec. 63.9(c)..................... Request for Compliance Can request if cannot Yes.

Extension. comply by date or if

installed best available

control technology or

lowest achievable emission

rate (BACT/LAER).

Sec. 63.9(d)..................... Notification of For sources that commence Yes.

Special Compliance construction between

Requirements for New proposal and promulgation

Sources. and want to comply 3 years

after effective date.Sec. 63.9(e)..................... Notification of Notify Administrator 60 Yes.

Performance Test. days prior.Sec. 63.9(f)..................... Notification of VE/ Notify Administrator 30 No.

Opacity Test. days prior.Sec. 63.9(g)..................... Additional Notification of performance Yes; however, there

Notifications When evaluation; notification are no opacity

Using CMS. about use of COMS data; standards.

notification that exceeded

criterion for relative

(1)-(6).............. Notification of Contents due 60 days after Yes; however, (1)

Compliance Status. end of performance test or there are no opacity

other compliance standards and (2) all

demonstration, except for initial Notification

opacity/visible emissions, of Compliance Status,

which are due 30 days including all

after; when to submit to performance test

Federal vs. State data, are to be

authority. submitted at the same

time, either within

240 days after the

compliance date or

within 60 days after

the last performance

test demonstrating

compliance has been

completed, whichever

occurs first.Sec. 63.9(i)..................... Adjustment of Procedures for Yes.

Submittal Deadlines. Administrator to approve

change in when

notifications must be

submitted.Sec. 63.9(j)..................... Change in Previous Must submit within 15 days No. These changes will

Information. after the change. be reported in the

first and subsequent

compliance reports.Sec. 63.10(a).................... Recordkeeping/ Applies to all, unless Yes.

Reporting. compliance extension; when

to submit to Federal vs.

State authority;

procedures for owners of

more than one source.Sec. 63.10(b)(1)................. Recordkeeping/ General requirements; keep Yes.

Reporting. all records readily

available; keep for 5

years.Sec. 63.10(b)(2)(i)-(iv)......... Records Related to Occurrence of each for Yes.

Startup, Shutdown, operations (process

and Malfunction. equipment); occurrence of

each malfunction of air

pollution control

equipment; maintenance on

air pollution control

equipment; actions during

SSM.Sec. 63.10(b)(2)(vi)-(xi)........ CMS Records........... Malfunctions, inoperative, Yes.

out-of-control periods.Sec. 63.10(b)(2)(xii)............ Records............... Records when under waiver.. Yes.Sec. 63.10(b)(2)(xiii)........... Records............... Records when using Yes.

alternative to relative

accuracy test.Sec. 63.10(b)(2)(xiv)............ Records............... All documentation Yes.

supporting initial

notification and

notification of compliance

status.Sec. 63.10(b)(3)................. Records............... Applicability Yes.

determinations.Sec. 63.10(c).................... Records............... Additional records for CMS. Yes.Sec. 63.10(d)(1)................. General Reporting Requirement to report...... Yes.

Requirements.Sec. 63.10(d)(2)................. Report of Performance When to submit to Federal Yes.

Test Results. or State authority.Sec. 63.10(d)(3)................. Reporting Opacity or What to report and when.... Yes.

VE Observations.Sec. 63.10(d)(4)................. Progress Reports...... Must submit progress Yes.

reports on schedule if

under compliance extension.Sec. 63.10(d)(5)................. SSM Reports........... Contents and submission.... Yes.Sec. 63.10(e)(1)-(2)............. Additional CMS Reports Must report results for Yes; however, COMS are

each CEMS on a unit; not applicable.

written copy of CMS

performance evaluation; 2-

3 copies of COMS

performance evaluation.Sec. 63.10(e)(3)(i)-(iii)........ Reports............... Schedule for reporting Yes; however, note

excess emissions and that the title of the

parameter monitor report is the

exceedance (now defined as compliance report;

deviations). deviations include

excess emissions and

parameter

exceedances.

Sec. 63.10(e)(3)(iv)-(v)......... Excess Emissions Requirement to revert to Yes.

Reports. quarterly submission if

there is an excess

emissions or parameter

monitoring exceedance (now

defined as deviations);

provision to request

semiannual reporting after

compliance for 1 year;

submit report by 30th day

following end of quarter

or calendar half; if there

has not been an exceedance

or excess emissions (now

defined as deviations),

report contents in a

statement that there have

been no deviations; must

submit report containing

all of the information in

Sec. Sec. 63.8(c)(7)-

(8) and 63.10(c)(5)-(13).Sec. 63.10(e)(3)(vi)-(viii)...... Excess Emissions Requirements for reporting Yes.

Report and Summary excess emissions for CMS

Report. (now called deviations);

requires all of the

information in Sec. Sec.

63.10(c)(5)-(13) and

63.8(c)(7)-(8).Sec. 63.10(e)(4)................. Reporting COMS Data... Must submit COMS data with No.

performance test data.Sec. 63.10(f).................... Waiver for Procedures for Yes.

Recordkeeping/ Administrator to waive.

Reporting.Sec. 63.11(b).................... Flares................ Requirements for flares.... Yes; Sec. 63.987

requirements apply,

and the section

references Sec.

63.11(b).Sec. 63.11(c), (d), and (e)...... Control and work Alternative work practice Yes.

practice requirements. for equipment leaks.Sec. 63.12....................... Delegation............ State authority to enforce Yes.

standards.Sec. 63.13....................... Addresses............. Addresses where reports, Yes.

notifications, and

requests are sent.Sec. 63.14....................... Incorporation by Test methods incorporated Yes.

Reference. by reference.Sec. 63.15....................... Availability of Public and confidential Yes.

Information. information.---------------------------------------------------------------------------------------------------------------- [69 FR 5063, Feb. 3, 2004, as amended at 71 FR 20463, Apr. 20, 2006; 71 FR 42924, July 28, 2006; 73 FR 78215, Dec. 22, 2008]

Subpart FFFF_National Emission Standards for Hazardous Air Pollutants:

Miscellaneous Organic Chemical Manufacturing

Source: 68 FR 63888, Nov. 10, 2003, unless otherwise noted.

What This Subpart Covers