(a) Each owner or operator of loading racks at a bulk gasoline terminal subject to the provisions of this subpart shall comply with the requirements in Sec. 60.502 of this chapter except for paragraphs (b), (c), and (j) of that section. For purposes of this section, the term ``affected facility'' used in Sec. 60.502 of this chapter means the loading racks that load gasoline cargo tanks at the bulk gasoline terminals subject to the provisions of this subpart.
(b) Emissions to the atmosphere from the vapor collection and processing systems due to the loading of gasoline cargo tanks shall not exceed 10 milligrams of total organic compounds per liter of gasoline loaded.
(c) Each owner or operator of a bulk gasoline terminal subject to the provisions of this subpart shall comply with Sec. 60.502(e) of this chapter as follows:
(1) For the purposes of this section, the term ``tank truck'' as used in Sec. 60.502(e) of this chapter means ``cargo tank.''
(2) Section 60.502(e)(5) of this chapter is changed to read: The terminal owner or operator shall take steps assuring that the nonvapor-tight gasoline cargo tank will not be reloaded at the facility until vapor tightness documentation for that gasoline cargo tank is obtained which documents that:
(i) The tank truck or railcar gasoline cargo tank meets the test requirements in Sec. 63.425(e), or the railcar gasoline cargo tank meets applicable test requirements in Sec. 63.425(i);
(ii) For each gasoline cargo tank failing the test in Sec. 63.425 (f) or (g) at the facility, the cargo tank either:
(A) Before repair work is performed on the cargo tank, meets the test requirements in Sec. 63.425 (g) or (h), or
(B) After repair work is performed on the cargo tank before or during the tests in Sec. 63.425 (g) or (h), subsequently passes the annual certification test described in Sec. 63.425(e).
(d) Each owner or operator shall meet the requirements in all paragraphs of this section as expeditiously as practicable, but no later than December 15, 1997, at existing facilities and upon startup for new facilities.
(e) As an alternative to 40 CFR 60.502(h) and (i) as specified in paragraph (a) of this section, the owner or operator may comply with paragraphs (e)(1) and (2) of this section.
(1) The owner or operator shall design and operate the vapor processing system, vapor collection system, and liquid loading equipment to prevent gauge pressure in the railcar gasoline cargo tank from exceeding the applicable test limits in Sec. 63.425(e) and (i) during product loading. This level is not to be exceeded when measured by the procedures specified in 40 CFR 60.503(d) of this chapter.
(2) No pressure-vacuum vent in the bulk gasoline terminal's vapor processing system or vapor collection system may begin to open at a system pressure less than the applicable test limits in Sec. 63.425(e) or (i). [59 FR 64318, Dec. 14, 1994; 60 FR 32913, June 26, 1995, as amended at 68 FR 70965, Dec. 19, 2003]