Code of Federal Regulations (alpha)

CFR /  Title 40  /  Part 98  /  Sec. 98.303 Calculating GHG emissions.

(a) Calculate the annual SF6 and PFC emissions using the mass-balance approach in Equation DD-1 of this section: [GRAPHIC] [TIFF OMITTED] TR01DE10.053 where: Decrease in SF6 Inventory = (pounds of SF6 stored

in containers, but not in energized equipment, at the

beginning of the year) - (pounds of SF6 stored in

containers, but not in energized equipment, at the end of the

year).Acquisitions of SF6 = (pounds of SF6 purchased

from chemical producers or distributors in bulk) + (pounds of

SF6 purchased from equipment manufacturers or

distributors with or inside equipment, including hermetically

sealed-pressure switchgear) + (pounds of SF6

returned to facility after off-site recycling).Disbursements of SF6 = (pounds of SF6 in bulk and

contained in equipment that is sold to other entities) +

(pounds of SF6 returned to suppliers) + (pounds of

SF6 sent off site for recycling) + (pounds of

SF6 sent off-site for destruction).Net Increase in Total Nameplate Capacity of Equipment Operated = (The

Nameplate Capacity of new equipment in pounds, including

hermetically sealed-pressure switchgear) - (Nameplate Capacity

of retiring equipment in pounds, including hermetically

sealed-pressure switchgear). (Note that Nameplate Capacity

refers to the full and proper charge of equipment rather than

to the actual charge, which may reflect leakage).

(b) Use Equation DD-1 of this section to estimate emissions of PFCs from power transformers, substituting the relevant PFC(s) for SF6 in the equation.