CFR /  Title 46  /  Part 112  /  Sec. 112.05-5 Emergency power source.

(a) The emergency power source must meet table 112.05-5(a) and have the capacity to supply all loads that are simultaneously connected to it, except a load on a bus-tie to the main switchboard or non-required loads that are connected in accordance with Sec. 112.05-1(c).

Table 112.05-5(a)------------------------------------------------------------------------

Period of

Type of emergency operation and

Size of vessel and service power source or minimum capacity

lighting of emergency

power------------------------------------------------------------------------Passenger vessels:

Ocean, Great Lakes, or Temporary emergency 36 hours.\1 2\

coastwise; or on an power source; and

international voyage. final emergency power

source (automatically

connected storage

battery or an

automatically started

generator).

Other than Ocean, Great Final emergency power 8 hours or twice

Lakes, or coastwise and not source (automatically the time of

on an international voyage. connected storage run, whichever

battery or an is less.\2\

automatically started

generator).Cargo vessels; miscellaneous

self-propelled vessels;

tankships; barges with

sleeping accommodations for

more than 6 persons; mobile

offshore drilling units; and

oceanographic vessels:

Ocean, Great Lakes, or Final emergency power 18 hours.\1 2\

coastwise and 500 GT or source (automatically

more; on an international connected storage

voyage and 500 GT or more; battery or an

or all waters and 1600 GT automatically started

or more. generator).

Ocean, Great Lakes, or Emergency lighting 6 hours or twice

coastwise and less than 500 provided by an the time of

GT; or other than ocean, automatically run, whichever

Great Lakes, or coastwise, connected or manually is less.

300 GT or more but less controlled storage

than 1600 GT, and not on an battery;

international voyage.. automatically or

manually started

generator; or relay-

controlled, battery-

operated lanterns.\3

4\.------------------------------------------------------------------------\1\ A 12-hour power supply may be especially considered for vessels

engaged regularly in voyages of short duration.\2\ The capacity for the operation of the steering gear, as required by

Sec. 111.93, is for a period of 30 minutes continuous operation.\3\ The emergency lighting requirements of Sec. 112.15-1 (b), (c),

(f), and (g) must be met.\4\ Requirements of Subpart 112.39 must be met by the relay-controlled,

battery-operated lanterns.

(b) The emergency power source must be independent of the ship's service lighting and powerplant and propulsion plant, except for the compressed air starting means allowed in Sec. 112.50-7(c)(3)(i). A stop control for an emergency generator must be only in the space that has the emergency generator, except a remote mechanical reach rod is permitted for the fuel oil shut-off valve to an independent fuel oil tank located in the space.

(c) The complete emergency installation must function at full rated power when the vessel is upright or inclined to the maximum angle of heel that results from the assumed damage defined in 33 CFR part 155 or in subchapter S of this chapter for the specific vessel type or 22.5 degrees, whichever is greater; when the trim of the ship is 10 degrees, either in the fore or aft direction, or is in any combination of angles within those limits.

(d) The emergency power source, its associated transforming equipment, and the emergency switchboard must be located aft of the collision bulkhead, outside of the machinery casing, and above the uppermost continuous deck. Each compartment containing this equipment must be readily accessible from the open deck and must not contain machinery not associated with, or equipment not in support of, the normal operation of the emergency power source. Equipment in support of the normal operation of the emergency power source includes, but is not limited to, ventilation fans, CO2 bottles, space heaters, and internal communication devices, such as sound powered phones.

(e) No compartment that has an emergency power source or its vital components may adjoin a Category A machinery space or those spaces containing the main source of electrical power and its vital components.

(f) Except for a cable for connecting equipment in the engineroom or boilerroom, no cable supplied from the emergency switchboard may penetrate the boundaries of the engineroom, boilerroom, uptakes, or casings of these spaces. These cables must be kept clear of the bulkheads and decks forming these boundaries. No emergency circuit in an engineroom or a boilerroom may supply equipment in any other space.

(g) The emergency switchboard must be as near as practicable to the emergency power source but not in the same space as a battery emergency power source.

(h) If the emergency power source is a generator, the emergency switchboard must be in the same space as the emergency power source.

(i) The prime mover of an emergency generator must be either a diesel engine or a gas turbine. [CGD 74-125A, 47 FR 15267, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28286, June 4, 1996; 62 FR 23910, May 1, 1997]