(a) The fire detecting system shall be divided into separate zones to restrict the area covered by any particular alarm signal.
(b) All spaces in a fire detecting zone shall be accessible from one to another without leaving the deck involved. All doors in watertight subdivision bulkheads and main vertical zone bulkheads shall be assumed closed for the purpose of this requirement.
(c) The fire detecting zone shall not include spaces on more than one deck, except:
(1) Adjacent and communicating spaces on different decks in the ends of the vessel having a combined ceiling area of not more than 3,000 square feet.
(2) Isolated rooms or lockers in such spaces as mast houses, wheelhouse top, etc., which are easily communicable with the area of the fire-detecting circuit to which they are connected.
(3) Systems with indicators for individual spaces.
(d) The fire detecting zone shall not contain more than 50 protected rooms or spaces.