Code of Federal Regulations (alpha)

CFR /  Title 49  /  Part 230  /  Sec. 230.116 Oil tanks.

The oil tanks on oil burning steam locomotives shall be maintained free from leaks. The oil supply pipe shall be equipped with a safety cut-off device that:

(a) Is located adjacent to the fuel supply tank or in another safe location;

(b) Closes automatically when tripped and that can be reset without hazard; and

(c) Can be hand operated from clearly marked locations, one inside the cab and one accessible from the ground on each exterior side of the steam locomotive.

Sec. Appendix A to Part 230--Inspection Requirements

The lists in this appendix are intended as guidance only. Adherence to this list does not relieve the steam locomotive owner and/or operator of responsibility for either: (1) Completing the inspection and maintenance requirements described in this part; or (2) ensuring that the steam locomotive, tender and its parts and appurtenances are safe and suitable for service.

Daily Inspection Requirements; Sec. 230.13

1. Observance of lifting pressure of the lowest safety valve.

2. Testing of water glasses and gauge cocks.*

3. Inspection of tubular water glass shields.

4. Inspection of all cab lamps.*

5. Inspection of boiler feedwater delivery systems.*

6. Inspection of lagging for indication of leaks.

7. Inspection for leaks obstructing vision of engine crew.

8. Observance of compressor(s) and governor to ascertain proper operation.*

9. Inspection of brake and signal equipment.*

10. Inspection of brake cylinders for piston travel.

11. Inspection of foundation brake gear.

12. Inspection of sanders.*

13. Inspection of draw gear and chafing irons.

14. Inspection of draft gear.

15. Inspection of crossheads and guides.

16. Inspection of piston rods and fasteners.

17. Inspection of main, side, and valve motion rods.

18. Inspection of headlights and classification lamps.*

19. Inspection of running gear.

20. Inspection of tender frames and tanks.

21. Inspection of tender trucks for amount of side bearing clearance.

Note: All items marked (*) should be checked at the beginning of each day the locomotive is used.

31 Service Day Inspection Requirements; Sec. 230.14

1. Washing of boiler.

2. Cleaning and inspection of water glass valves and gauge cocks.

3. Cleaning, washing and inspection of arch tubes, water bar tubes, circulators and siphons.

4. Removal and inspection of all washout and water tube plugs.

5. Testing of all staybolts.

6. Removal, cleaning and inspection of fusible plugs (if any).

92 Service Day Inspection Requirements; Sec. 230.15

1. Removal and testing of all air and steam gauges.

2. Cleaning of steam gauge siphon pipe.

3. Renewal of tubular water glasses.

4. Testing and adjusting of safety relief valves.

5. Testing of main reservoir and brake cylinder leakage.

6. Entering and inspection of tender tank interior.

Annual Inspection Requirements; Sec. 230.16

1. Testing of thickness of arch and water bar tubes (arch brick to be removed)

2. Hydrostatic testing of boiler.

3. Testing of all staybolts.

4. Interior inspection of boiler.

5. Thickness verification of dry pipes.

6. Smoke box inspection.

7. Main reservoir hammer or UT testing and hydrostatic testing (for non-welded and drilled main reservoirs)

8. Removal and inspection of steam locomotive drawbar(s) and pins (NDE testing other than merely visual)

9. Inspection of longitudinal lap joint boiler seams.

5 Year Inspection Requirements; Sec. 230.16

1. Inspection of flexible staybolt caps and sleeves.

1472 Service Day Inspection Requirements; Sec. 230.17

1. Removal of boiler flues (as necessary) and cleaning of boiler interior.

2. Removal of jacket and lagging and inspection of boiler interior and exterior.

3. Hydrostatic testing of boiler.

4. Thickness verification (boiler survey) and recomputation and update of steam locomotive specification card, (FRA Form No. 4).

Appendix B to Part 230--Diagrams and Drawings[GRAPHIC] [TIFF OMITTED] TR17NO99.015 [GRAPHIC] [TIFF OMITTED] TR17NO99.016 [GRAPHIC] [TIFF OMITTED] TR17NO99.017 [GRAPHIC] [TIFF OMITTED] TR17NO99.018 [GRAPHIC] [TIFF OMITTED] TR17NO99.019 [GRAPHIC] [TIFF OMITTED] TR17NO99.020 [GRAPHIC] [TIFF OMITTED] TR17NO99.021 [GRAPHIC] [TIFF OMITTED] TR17NO99.022 [GRAPHIC] [TIFF OMITTED] TR17NO99.023 [GRAPHIC] [TIFF OMITTED] TR17NO99.024 [GRAPHIC] [TIFF OMITTED] TR17NO99.025 [GRAPHIC] [TIFF OMITTED] TR17NO99.026 [GRAPHIC] [TIFF OMITTED] TR17NO99.027 [GRAPHIC] [TIFF OMITTED] TR17NO99.028 [GRAPHIC] [TIFF OMITTED] TR17NO99.029 [GRAPHIC] [TIFF OMITTED] TR17NO99.030 [GRAPHIC] [TIFF OMITTED] TR17NO99.031 [GRAPHIC] [TIFF OMITTED] TR17NO99.032 [GRAPHIC] [TIFF OMITTED] TR17NO99.033

Sec. Appendix C to Part 230--FRA Inspection Forms[GRAPHIC] [TIFF OMITTED] TR17NO99.034 [GRAPHIC] [TIFF OMITTED] TR17NO99.035 [GRAPHIC] [TIFF OMITTED] TR17NO99.036 [GRAPHIC] [TIFF OMITTED] TR21JY05.063 [GRAPHIC] [TIFF OMITTED] TR21JY05.064 [GRAPHIC] [TIFF OMITTED] TR21JY05.065 [GRAPHIC] [TIFF OMITTED] TR21JY05.066 [GRAPHIC] [TIFF OMITTED] TR21JY05.067 [GRAPHIC] [TIFF OMITTED] TR21JY05.068 [GRAPHIC] [TIFF OMITTED] TR17NO99.043 [GRAPHIC] [TIFF OMITTED] TR17NO99.044 [64 FR 62865, Nov. 17, 1999, as amended at 70 FR 41996, July 21, 2005]

Sec. Appendix D to Part 230--Civil Penalty Schedule ------------------------------------------------------------------------

Willful

Section Violation violation------------------------------------------------------------------------

Subpart A--General

230.11 Repair of non-complying conditions:

(a) Failure to repair non-complying $1,000 $2,500

steam locomotive prior to use in

service................................

(b) Failure of owner and/or operator to 1,000 1,500

approve repairs made prior to use of

steam locomotive.......................230.12 Movement of non-complying steam (\1\) (\1\)

locomotive:230.13 Daily inspection:

(a) (b):

(1) Inspection overdue.............. 1,500 3,000

(2) Inspection not performed by 1,000 1,500

qualified person...................

(c) Inspection report not made, 1,000 1,500

improperly executed or not retained....230.14 Thirty-one service day inspection:

(a):

(1) Inspection overdue.............. 1,500 3,000

(2) Inspection not performed by

qualified person...................

(b) Failure to notify FRA............... 1,000 1,500

(c) Inspection report not made, 1,000 1,500

improperly executed, not properly filed230.15 Ninety-two service day inspection:

(a):

(1) Inspection overdue.............. 1,500 3,000

(2) Inspection not performed by 1,000 1,500

qualified person...................

(b) Inspection report not made, 1,000 1,500

improperly executed, not properly filed230.16 Annual inspection:

(a):

(1) Inspection overdue.............. 1,500 3,000

(2) Inspection not performed by 1,000 1,500

qualified person...................

(b) Failure to notify FRA............... 1,000 1,500

(c) Inspection report not made, 1,000 1,500

improperly executed, not properly filed230.17 One thousand four hundred seventy-two

service day inspection:

(a):

(1) Inspection overdue.............. 1,500 3,000

(2) Inspection not performed by 1,250 2,000

qualified person...................

(b) Inspection report not made, 1,000 1,500

improperly executed, not properly

maintained, not properly filed.........230.18 Service days:

(a) Service day record not available for 1,000 1,500

inspection.............................

(b) Failure to file service day report 1,000 1,500

with FRA Regional Administrator........

(c) Failure to complete all 1,472 1,500 3,000

service day inspection items prior to

returning retired steam locomotive to

service................................230.19 Posting of forms:

(a) FRA Form No. 1:

(1) FRA Form No. 1 not properly 1,000 1,500

filled out.........................

(2) FRA Form No. 1 not properly 1,000 1,500

displayed..........................

(b) FRA Form No. 3:

(1) FRA Form No. 3 not properly 1,000 1,500

filled out.........................

(2) FRA Form No. 3 not properly 1,000 1,500

displayed..........................230.20 Alteration and repair reports:

(a) Alterations:

(1) Failure to properly file FRA 1,000 1,500

Form No. 19 with FRA Regional

Administrator......................

(2) FRA Form No. 19 not properly 1,000 1,500

filled out.........................

(3) FRA Form No. 19 not properly 1,000 1,500

maintained.........................

(b) Repairs to unstayed portions of the

boiler:

(1) FRA Form No. 19 not properly 1,000 1,500

filled out.........................

(2) FRA Form No. 19 not properly 1,000 1,500

maintained.........................

(c) Repairs to stayed portions of the

boiler:

(1) FRA Form No. 19 not properly 1,000 1,500

filled out.........................

(2) FRA Form No. 19 not properly 1,000 1,500

maintained.........................230.21 Failure to properly document steam 1,000 1,500

locomotive number Change...................

Subpart B--Boilers and Appurtenances

230.22 Failure to properly report accident 1,500 2,500

resulting from failure of steam locomotive

boiler or part or appurtenance thereof.....230.23 Responsibility for general

construction and safe working pressure:

(a) Failure to properly establish safe 5,000 10,000

working pressure for steam locomotive

boiler.................................

(b) Placing steam locomotive in service 5,000 10,000

before safe working pressure for boiler

has been established...................230.24 Maximum allowable stress values on

boiler components:

(a) Use of materials not of sufficient 1,000 2,000

tensile strength.......................

(b) Use of a safety factor value of less 2,000 4,000

than 4 when using the code of original

construction in boiler calculations....230.25 Maximum allowable stresses on stays

and braces:

(a) Exceeding allowable stress values on 1,000 2,000

fire box and/or combustion chamber.....

(b) Exceeding allowable stress values on 1,000 2,000

round, rectangular or gusset braces....230.29 Inspection and repair:

(a):

(1) Failure of owner and/or operator 1,500 3,000

to inspect and repair any steam

locomotive boiler and/or

appurtenance under control thereof.

(2) Failure to remove steam 2,500 5,000

locomotive from service when

considered necessary to do so......

(b):

(1) Failure of perform repairs in 2,000 4,000

accordance with accepted industry

standards..........................

(2) Owner and/or operator returning 2,000 4,000

steam locomotive boiler and/or

appurtenances to service before

they are in good condition and safe

and suitable for service...........230.30 Lap-joint seam boilers, Failure to 2,000 4,000

properly inspect...........................230.31 Flues to be removed:

(a):

(1) Failure to remove all flues when 1,500 3,000

inspecting boiler..................

(2) Failure to enter boiler and 1,500 3,000

clean and inspect..................

(b) Failure to remove superheater flues 1,000 2,000

when deemed necessary to do so.........230.32 Time and method of inspection:

(a) Failure to perform 1,472 service day 1,500 3,000

inspection when required to do so......

(b) Failure to properly inspect boiler 1,500 3,000

during 1,472 service day inspection....230.33 Welded repairs and alterations:

(a) Failure to obtain permission before 1,500 3,000

welding on unstayed portions of boiler

containing alloy or carbon steel with

carbon content over .25 percent carbon.

(b) Failure to perform welding on 1,500 3,000

unstayed portions of boiler containing

carbon steel not exceeding .25 percent

carbon in accordance with a nationally

accepted standard for boiler repairs...

(c):

(1) Failure to submit written 1,500 3,000

request for approval before

performing weld buildup on wasted

areas of unstayed boiler surfaces

that exceed 100 square inches or

the smaller of 25 percent of

minimum required wall thickness or

\1/2\ inch.........................

(2) Repairing wasted sheets......... 1,500 3,000230.34 Riveted repairs and alterations:

(a) Failure to obtain approval before 1,500 3,000

making riveted alterations on unstayed

portions of the boiler; failure to do

riveting in accordance with established

railroad practices or accepted national

standards for boiler repairs...........

(b) Failure to perform riveted repairs 1,500 3,000

on unstayed boiler portions in

accordance with established railroad

practices or accepted national

standards for boiler repairs...........

(c) Failure to perform riveted repairs 1,000 2,000

on stayed boiler portions in accordance

with established railroad practices or

accepted national standards for boiler

repairs................................230.35 Failure to raise temperature of steam 1,000 2,000

locomotive boiler to 70 degrees F. before

applying hydrostatic pressure to the boiler230.36 Hydrostatic testing of boilers:

(a) Failure to perform hydrostatic test 1,500 3,000

of boiler as required..................

(b) Failure to properly perform 1,500 3,000

hydrostatic test.......................

(c) Failure to properly inspect boiler 1,500 3,000

after conducting hydrostatic test above

MAWP...................................230.37 Failure to perform proper steam test 1,000 2,000

or inspection of boiler after completion of

repair or alteration to boiler.............230.38 Telltale holes:

(a) Failure to have telltale holes as 1,000 2,000

required in staybolts..................

(b) Failure to have proper telltale 1,000 2,000

holes in reduced body staybolts........

(c) Failure to keep telltales holes when 1,000 2,000

so required............................230.39 Broken staybolts:

(a) Boiler in service with excess number 1,500 3,000

of broken staybolts....................

(b) Failure to replace staybolts when 1,500 3,000

required to do so; to properly replace

staybolts when so required; to inspect

adjacent staybolts when replacing

broken staybolts.......................

(c) Failure to count leaking, plugged, 1,500 3,000

or missing telltale holes as broken

staybolts..............................

(d) Closing telltale holes by prohibited 1,500 3,000

means..................................230.40 Time and method of staybolt testing:

(a) Failure to hammer test staybolts 1,000 2,000

when so required.......................

(b) Failure to properly hammer test 1,000 2,000

staybolts..............................230.41 Flexible staybolts with caps:

(a) Failure to inspect flexible 1,000 2,000

staybolts as required..................

(b) Failure to replace broken flexible 1,000 2,000

staybolts; failure to close inner ends

of telltale holes as required..........

(c) Failure to report removal of 1,000 2,000

flexible staybolts caps and other tests

on FRA Form No. 3 when so required.....

(d) Failure to remove staybolt caps or 1,000 2,000

otherwise test when FRA inspector or

steam locomotive owner and/or operator

consider it necessary to do so.........230.42 Failure to have accurate boiler steam 2,000 4,000

gauge where engine crew can conveniently

read.......................................230.43 Failure to have gauge siphon of 1,000 2,000

proper capacity on steam gauge supply pipe;

failure to properly clean, maintain the

steam gauge supply pipe....................

230.44 Failure to test steam gauge when so 1,000 2,000

required...................................230.45 Failure to properly test and/or set 1,000 2,000

steam gauge................................230.46 Failure to attach to boiler backhead 1,000 1,500

metal badge plate showing allowable steam

pressure...................................230.47 Boiler Number:

(a) (b) (c) Failure to stamp builder's 1,000 1,500

number on boiler when number is known..230.48 Number and capacity of safety relief

valves:

(a) Failure to equip steam locomotive 2,500 5,000

boiler with proper safety relief valves

(b) Failure to provide additional safety 3,000 6,000

relief valve capacity when so required.230.49 Setting of safety relief valves:

(a) Safety relief valve(s) set and/or 2,500 5,000

adjusted by person not competent to do

so.....................................

(b) Safety relief valve(s) not set to 2,500 5,000

open at prescribed pressure(s).........

(c) Safety relief valve(s) not properly 3,000 6,000

set....................................

(d) Set pressure of lowest safety relief 1,000 2,000

valve not properly indicated...........230.50 Failure to test and adjust safety 1,500 3,000

relief valves when required to do so.......230.51 Failure to equip steam locomotive 1,000 2,000

boiler with at least 2 properly installed

water glasses..............................230.52 Failure to properly equip water 2,000 4,000

glasses....................................230.53 Failure to properly clean water glass 1,000 2,000

valves and/or gauge cocks when required to

do so......................................230.54 Testing and maintenance:

(a) Failure to properly test water 1,000 2,000

glasses and/or gauge cocks.............

(b) Failure to properly maintain gauge 1,500 3,000

cocks, water column drain valves, and/

or water glass valves..................230.55 Tubular type water and lubricator

glasses and shields:

(a) Failure to renew tubular type water 1,000 2,000

glasses as required....................

(b) Failure to properly shield tubular 1,000 2,000

water glasses and/or lubricator glasses

(c) Failure to properly locate and/or 1,000 2,000

maintain water glasses and/or water

glass shields..........................230.56 Failure to equip water glass with 1,000 2,000

suitable lamp..............................230.57 Injectors and feedwater pumps:

(a) Failure to equip steam locomotive 3,000 6,000

with proper means for delivering water

to the boiler..........................

(b) Failure to properly test and/or 2,500 5,000

maintain injectors, feedwater pumps,

boiler checks, delivery pipes, feed

water pipes, tank hose, tank valves....

(c) Failure to properly brace injectors, 1,000 2,000

feedwater pumps, and/or associated

piping.................................230.58 Flue plugs:

(a) Plugging flue plugs when not 1,000 2,000

otherwise permitted....................

(b) Improperly plugging flue plugs, when 1,000 2,000

otherwise permitted....................230.59 Failure to remove and properly clean 1,500 3,000

fusible boiler plugs when required to do

so; failure to properly note removal.......230.60 Time of washing:

(a) Failure to thoroughly wash boiler 1,000 2,000

when required to do so.................

(b) Failure to remove washout plugs, 1,500 3,000

arch tube plugs, thermic siphon plugs,

circulator plugs, water bar plugs when

washing locomotive boiler..............

(c) Failure to examine and/or properly 1,500 3,000

maintain washout plugs washout plug

sleeves, threaded openings.............

(d) Failure to clean fusible plugs when 1,500 3,000

required to do so......................230.61 Arch tubes, water bar tubes,

circulators and thermic siphons:

(a) Failure to clean, wash, inspect arch 1,000 2,000

tubes, water bar tubes, circulators and

thermic siphons as required............

(b) Failure to renew arch tubes, water 1,500 3,000

bar tubes; failure to repair or renew

circulators, thermic siphons when

required...............................

(c) Failure to properly inspect and/or 1,500 3,000

replace as necessary arch tubes, water

bar tubes, circulators.................230.62 Failure to properly inspect and/or 2,500 5,000

repair or replace as necessary dry pipes

subject to pressure........................230.63 Failure to properly inspect smoke 1,500 3,000

box, steam pipes, pressure parts when

required to do so..........................230.64 Failure to remove from service steam 1,500 3,000

locomotive boiler leaking under lagging

from condition which may reduce safety and/

or repair the boiler before returning to

service....................................230.65 Failure to keep steam locomotive 1,000 2,000

boiler, piping, appurtenances in repair so

steam does not obscure vision..............230.66 Failure to properly oversee general 1,000 2,000

design, construction, maintenance of steam

locomotive(s) and tender(s)................230.67 Failure to ensure all steam 2,500 5,000

locomotives and tenders are properly

inspected and repaired and/or all defects

are properly repaired and steam locomotive

and/or tender are in good condition, safe

and suitable for service before being

returned to service........................230.68 Failure to equip steam locomotive 1,000 1,500

that operates in excess of 20 miles per

hour over the general system with speed

indicator maintained to ensure accurate

functioning................................230.69 Failure to equip steam locomotive 1,000 2,000

with properly supported ash pan with

operating mechanism that may be safely

operated and securely closed...............230.70 Safe condition:

(a) Failure to perform proper pre- 1,000 2,000

departure inspection when so required..

(b) Failure to properly equip steam 1,000 2,000

locomotive with brake pipe valve

clearly identified as ``Emergency Brake

Valve''................................230.71 Orifice testing of air compressors:..

(a)(b):

Failure to properly test and/or 1,000 2,000

maintain air compressor(s) capacity

230.72 Testing main reservoirs:

(a) Failure to properly test main 1,000 2,000

reservoir(s) when required.............

(b) Impermissibly or improperly drilling 1,000 2,000

main reservoir.........................

(c) Impermissibly using NDE method to 1,000 2,000

measure wall thickness of main

reservoir..............................

(d) Failure to use appropriate method of 1,500 3,000

NDE testing of wall thickness of welded

or riveted longitudinal lap seam main

reservoir(s); failure to withdraw main

reservoir(s) from service when testing

reveals insufficient wall thickness....230.73 Air gauges:

(a) Failure to equip steam locomotive 1,000 1,500

with properly located air gauge(s) that

are no more than 3 psi in error........

(b) Failure to test air gauge(s) when so 1,000 1,500

required...............................

(c) Failure to properly test air 1,000 1,500

gauge(s)...............................230.74 Failure to properly clean and/or test 1,000 1,500

all air brake valves, related dirt

collectors, filters when required to do so.230.75 Failure to properly stencil or 1,000 1,500

display date of testing and cleaning and

initials of shop or station performing work230.76 Piston travel:

(a) Insufficient minimum piston travel.. 1,000 1,500

(b) Excessive piston travel when steam 1,000 2,000

locomotive is stationary...............230.77 Foundation brake gear:

(a) Failure to properly maintain 1,000 2,000

foundation brake gear..................

(b) Foundation brake gear less than 2.5 1,000 2,000

inches above rail......................230.78 Leakage:

(a):

(1) Failure to test for leakage from 1,000 1,500

main reservoir or related piping as

required...........................

(2) Failure to repair excessive 1,000 2,000

leakage from main reservoir or

related piping leakage.............

(b) Failure to test for brake cylinder 1,000 1,500

as required............................

(c):

(1) Failure to test for leakage from 1,000 2,000

steam locomotive brake pipe as

required...........................

(2) Failure to repair excessive 1,000 2,000

brake pipe leakage.................230.79 Train signal system:

(1) Failure to test the train signal 1,000 1,500

system or other form of on-board

communication as required..........

(2) Failure to repair train signal 1,000 1,500

system or other on-board

communication when not safe or

suitable for service...............230.80 Cabs:

(a) Steam locomotive cab not safe and 1,000 2,000

suitable for service...................

(b) Steam pipes: Construction, 1,000 2,000

attachment.............................

(c) Oil-burning steam locomotive, cab- 1,000 1,500

enclosed...............................230.81 Cab aprons:

(a) Cab apron, general provisions....... 1,000 1,500

(b) Cab apron, insufficient width....... 1,000 1,500230.82 Fire doors:

(a) Safe and suitable for service, 1,000 2,000

general provisions.....................

(b) Construction and maintenance of 1,000 2,000

mechanically operated fire doors.......

(c) Construction and maintenance of hand- 1,000 2,000

operated fire doors....................230.83 Cylinder cocks:

(1) Failure to properly equip with 1,000 1,500

cylinder cocks.....................

(2) Failure to properly maintain 1,000 1,500

cylinder cocks.....................230.84 Sanders:

(1) Inoperable sanders.............. 1,000 1,500

(2) Failure to test sanders......... 1,000 1,500230.85 Audible warning devices:

(a) General provisions.................. 1,000 1,500

(b) Sound level measurements, Failure to 1,000 1,500

properly take..........................230.86 Required illumination:

(a) General provisions.................. 1,000 1,500

(b) Dimming device, Failure to properly 1,000 1,500

equip with.............................

(c) Multiple locomotives, Failure of 1,000 1,500

lead locomotive to display headlight...230.87 Cab lights: Failure to properly equip 1,000 2,000

with.......................................230.88 Throttles: Failure to properly 1,000 2,000

maintain, equip............................230.89 Reverse gear:

(a) General provisions.................. 1,000 2,000

(b) Air-operated power reverse gear..... 1,000 2,000

(c) Power reverse gear reservoirs....... 1,000 2,000230.90 Draw gear and draft systems:

(a) Maintenance and testing............. 1,000 1,500

(b) Safety bars and chains, general..... 1,000 1,500

(c) Safety bars and chains, minimum 1,000 1,500

length.................................

(d) Lost motion between steam locomotive 1,000 1,500

and tender.............................

(e) Spring buffers: Improper 1,000 1,500

application, compression...............230.91 Chafing irons: Improper application, 1,000 1,500

maintenance................................

230.92 Draw gear, draft systems: Improperly 1,000 1,500

maintained, fastened.......................230.93 Pistons and piston rods:

(a) Failure to properly inspect, 1,000 2,000

maintain, renew........................

(b) Fasteners: Failure to keep tight, 1,000 2,000

properly equip.........................230.94 Crossheads: Improperly maintained, 1,000 2,000

excess clearance...........................230.95 Guides: Failure to securely fasten, 1,000 2,000

properly maintain..........................230.96 Main, side, valve motion rods:

(a) General............................. 1,000 2,000

(b) Repairs.............................

(1) Failure to make in accordance 1,000 2,000

with accepted national standard....

(2) Failure to submit written 1,000 2,000

request for approval prior to

welding............................

(c) Bearings and bushings........... 1,000 1,500

(d) Rod side motion: Excessive motion... 1,000 1,500

(e) Oil, grease cups: Failure to 1,000 1,500

securely fasten, properly equip........

(f) Main rod bearings:

(1) excessive bore.................. 1,000 1,500

(2) excessive lost motion........... 1,000 1,500

(g) Side rod bearings, excessive bore... 1,000 1,500230.97 Crank pins:

(a) General provisions.................. 1,000 2,000

(b) Maintenance: Failure to maintain in 1,000 2,000

safe, suitable condition...............230.98 Driving, trailing, engine truck

axles:

(a) Condemning defects.................. 1,000 2,000

(b) Journal diameter: Failure to stamp 750 1,000

on end of axle.........................230.99 Tender truck axle: Insufficient 1,000 2,000

diameter...................................230.100 Defects in tender truck axles and

journals:

(a) Tender truck axle condemning defects 1,000 2,000

(b) Tender truck journal condemning 1,000 2,000

defects................................230.101 Steam locomotive driving journal

boxes:

(a) Driving journal boxes: Failure to 1,000 2,000

properly maintain......................

(b) Broken bearings: Failure to renew... 1,000 2,000

(c) Loose bearings: Failure to repair or 1,000 2,000

renew..................................230.102 Tender plain bearing journal boxes: 1,000 1,500

Failure to repair..........................230.103 Tender roller bearing journal boxes: 1,000 1,500

Failure to properly maintain...............230.104 Driving box shoes and wedges: 1,000 1,500

Failure to properly maintain...............230.105 Lateral motion:

(a) Condemning limits: Total lateral 1,000 1,500

motion in excess of....................

(b) Limits exceeded, failure to 1,000 1,500

demonstrate conditions require

additional lateral motion..............

(c) Interferes with other parts of steam 1,000 1,500

locomotive.............................230.106 Steam locomotive frame:

(a) Failure to properly inspect and/or 1,000 2,000

maintain...............................

(b) Broken frames, not properly patched 2,500 5,000

or secured.............................230.107 Tender frame and body:

(a) Failure to properly maintain........ 1,000 1,500

(b) Height difference between tender 1,000 1,500

deck and steam locomotive cab floor or

deck excessive.........................

(c) Gangway minimum width excessive..... 1,000 1,500

(d) Tender frame condemning defects..... 1,500 3,000230.108 Steam locomotive leading and

trailing trucks:

(a) Failure to properly maintain........ 1,000 1,500

(b) Safety chain, suitable safety chain 1,000 1,500

not provided...........................

(c) Insufficient truck clearance........ 1,000 2,000230.109 Tender trucks:

(a):

(1) Tender truck frames............. 1,000 2,000

(2) Tender truck center plate....... 1,000 2,000

(b) Tender truck bolsters: Failure to 1,500 3,000

properly maintain......................

(c) Condemning defects, springs and/or 1,000 2,000

spring rigging.........................

(d) Truck securing arrangement: Not 1,000 1,500

properly maintained....................

(e) Side bearings, truck centering 1,000 2,000

devices................................

(f) Friction side bearings: Run in 1,000 2,000

contact................................

(g):

(1) Side bearings, failure to equip 1,000 2,000

rear trucks with...................

(2) Insufficient clearance of....... 1,000 2,000230.110 Pilots:

(a) General provisions.................. 1,000 1,500

(b) Clearance, insufficient or excessive 1,000 1,500230.111 Spring rigging:

(a) Arrangement of springs and 1,000 2,000

equalizers.............................

(b) Spring or spring rigging condemning 1,000 2,000

defects................................230.112 Wheels and tires:

(a) Improperly Mounted, excess variance 1,500 3,000

in axle diameter.......................

(b) Out of gage......................... 1,000 2,000

(c) Flange distance variance, excessive. 1,000 2,000

(d) Tire thickness, insufficient........ 1,000 2,000

(e) Tire width, insufficient............ 1,000 2,000230.113 Wheels and tire defects:

(1) Failure to repair............... 1,000 2,000

(2) Welding on, except as otherwise 1,500 3,000

provided for.......................

(a) Cracks or breaks in................. 1,000 2,000

(b) Flat spots.......................... 1,000 2,000

(c) Chipped flange...................... 1,000 2,000

(d) Broken rim.......................... 1,000 2,000

(e) Shelled-out spots................... 1,000 2,000

(f) Seams............................... 1,000 2,000

(g) Worn flanges, excessive wear........ 1,000 2,000

(h) Worn treads, excessive wear......... 1,000 2,000

(i) Flange height, insufficient or 1,000 2,000

excessive..............................

(j) Rim thickness, insufficient......... 1,000 2,000

(k) Wheel diameter, excessive variance.. 1,000 2,000230.114 Wheel centers:

(a) Filling blocks and shims............ 1,000 2,000

(b) Wheel center condemning limits, 1,000 2,000

failure to repair......................

(c) Wheel center repairs................ 1,000 2,000

(d) Counterbalance maintenance.......... 1,000 2,000230.115 Feed water tanks:

(a) General provisions.................. 1,000 2,000

(b) Inspection frequency, failure to 1,000 1,500

inspect as required....................

(c) Top of tender: Improperly maintained 1,000 1,500

and/or equipped........................230.116 Oil tanks:

(1) Failure to properly maintain.... 2,500 5,000

(2) Failure to equip with complying 5,000 7,500

safety cut-off device..............------------------------------------------------------------------------\1\ Failure to observe any condition for movement set forth in Sec.

230.12 will deprive the railroad of the benefit of the movement-for-

repair provision and make the railroad and any responsible individuals

liable for penalty under the particular regulatory section(s)

concerning the substantive defect(s) present on the locomotive at the

time of movement. Failure to comply with Sec. 230.12 will result in

the lapse of any affected waiver.